Stop Operation Control
Stop Operation Control in Cooling Mode
Table 10: Stop Operation Control in Cooling Mode.
Component
Inverter Compressor
Fan
Main EEV
Subcooling EEV
Four-Way Valve
Stop Operation Control in Heating Mode
Table 11: Stop Operation Control in Heating Mode.
Component
Inverter Compressor
Fan
Main EEV
Subcooling EEV
Four-Way Valve
Oil Equalizing Control
Oil equalizing control prevents oil imbalance between the inverter compressors. If the oil level sensors detect different oil levels between the
compressors, then the oil equalizing EEV will open for five (5) minutes.

Stop Operation

Off
Stop
32 Pulse
16 Pulse
Off
Stop Operation
Off
Stop
32 Pulse
16 Pulse
Off
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
SPECIAL CONTROLS
Notes
-
-
-
Stop (Minimum Pulse)
-
Notes
-
-
-
Stop (Minimum Pulse)
When air temperature is >30°C (86°F)
Stop Operation