Summary List Of Best Practices - Trane BACnet MS/TP Installation, Operation And Maintenance Manual

Wiring and link performance, best practices and troubleshooting
Table of Contents

Advertisement

Summary List of Best Practices

Use the following summary list of best practices to quickly locate a specific topic.
Configuring and Wiring the BACnet
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
Setting the BACnet
11.
12.
14.
Total Number of Trane and Non-Trane Devices on a BACnet
15.
16.
17.
Custom Programming
18.
19.
20.
Custom Graphics
21.
Controller Software
22.
23.
Tools
24.
26.
BAS-SVX51L-EN
®
MS/TP Link
"Do not mix isolated and non-isolated device types on a single link.," p.
"BACnet® wiring must use a daisy-chain configuration.," p.
"Observe the maximum link length recommendation," p.
"Use a Tracer® BACnet® terminator at each end of the link.," p.
"Use the built-in terminator on the BCI-R when the BCI-R is the last node in the network.," p.
"Maintain consistent wiring polarity between devices.," p.
"Observe network cable and conductor termination best practices during installation.," p.
"Avoid sharing 24 Vac power between unit controllers.," p.
"Ensure that 24 Vac power supplies are consistently grounded.," p.
"Meet requirements when adding zone sensor communication stubs to a Tracer® UC400/Symbio™ 500.," p.
®
Device Addresses
"Set the rotary switch address on all unit controllers.," p.
"Ensure no duplicate rotary switch addresses exist on a BACnet® MS/TP link.," p.
"Sequentially address BACnet® MS/TP devices; leave no gaps.," p.
"Limit the quantity of devices on a link when there are both Trane and non-Trane devices on the link.," p.
"Populate BACnet® links evenly when 30+ devices are present.," p.
"Place Trane Communicating Thermostats on a separate link.," p.
"Limit Tracer® SC+ TGP2 run frequency.," p.
"Use event triggered TGP2 to reduce run frequency.," p.
"Use Tracer® SC+ System Applications for common calculations.," p.
"Limit number of points displayed on a Tracer® SC+ Custom Graphic.," p.
"Update all UC400 controllers to Version 4.15 firmware (or higher).," p.
"Always run the latest Tracer® SC+ software (v5.5 or higher).," p.
"Trane SerialSpy Protocol Analyzer Software to troubleshoot communication links.," p.
"High-performance volt meter.," p.
11.
11.
11.
13.
13.
13.
19.
®
Link
21.
21.
21.
22.
22.
9.
12.
13.
19.
19.
20.
21.
21.
22.
22.
14.
20.
5