Setting Rotary Addresses on the Tracer
The Tracer
BACnet
value assigned to the device at the factory.
Note: If you set the rotary switch values to a number between 001 and 419, the Tracer
To set the rotary switch values, use a small screwdriver to turn the three rotary switches on the Tracer
SC+ to a unique number between 001 and 419.
®
BACnet
MS/TP Device ID Assignment
Each unit controller must have a unique BACnet
calculating a unique device ID for each unit controller and then saving the device ID to memory in each
device.
For Tracer
following three sets of values:
•
•
•
The three values are joined together to form the BACnet
The following example in
Table 2.
Tracer
Tracer
Unit controller rotary switch value (38)
BACnet
For Tracer
of values:
•
•
Device ID Assignment for BACnet IP Devices
For devices connecting over BACnet
•
•
The following example in
Table 3.
BACnet
Unit controller rotary address (42)
BACnet
BAS-SVX51L-EN
®
SC+ has a set of three rotary switches on the front of the device, which are used to set the
®
Device ID. The rotary switch range is 1 to 419. Zero (0) cannot be used because it is the default
®
and the BACnet
MS/TP numbers will be calculated from that number.
®
SC and SC+ prior to version 5.4, BACnet
®
The Tracer
SC+ rotary switch value (1 to 419).
®
The Tracer
SC+ BACnet MS/TP link number (1 to 2).
The unit controller rotary switch value (1 to 127).
Table 2
Calculating the BACnet
®
SC+ rotary switch value (21)
®
®
SC+ BACnet
MS/TP link number (1)
®
Device ID: 211038
®
SC+ version 5.4 and higher, BACnet
The network number.
The unit controller 3 digit rotary switch.
®
The BACnet
network number for Ethernet 1. (This number can be changed by the user).
The unit controller rotary switch value. (The Tracer
®
BACnet
IP device IDs).
Table 3
Calculating the BACnet
®
network number Eth port 1 (1)
®
IP Device ID: 01042
®
SC+ System Controller
®
device ID. Tracer
®
MS/TP device IDs are calculated using the
®
device ID for the unit controller.
illustrates this process.
®
device ID
0
2
0
2
®
MS/TP device IDs are calculated using only two sets
®
®
IP, Tracer
SC+ calculates the device ID using the following:
®
SC rotary address is not used to calculate
illustrates this process using a Tracer
®
IP device ID
Best Practices
®
®
SC+ automates the process by
1
1
0
1
1
0
®
UC600 controller.
1
0
0
1
0
SC+ device ID
®
3
8
3
8
4
2
4
2
17