14.17 Compressor discharge high temperature protection control

This control detect compressor tank temperature (CU-4Z80/5Z90TBE) and perform the compressor frequency
restriction.
A
C
When the discharge temperature more than 108°C, the compressor stops.
If this conditions happens for 3 times within 30 minutes, "F97" is indicated.

14.18 Cooling Outdoor Air Temperature Control (Cool)

The compressor will be stopped to avoid compressor overloading.

14.19 Heating Outdoor Air Temperature Control (Heat)

The compressor will be stopped to avoid compressor overloading.
Comp stop
B
Comp freq
restricted
D
Comp freq free
Comp tank temp CU-4Z80/5Z90TBE
-10°C
Outdoor
Air
Temperature
-10°C
Outdoor
Air
Temperature
A
B
C
D
COMP. ON
-12°C
COMP. OFF
COMP. ON
-22°C
COMP. OFF
284
CU-4Z80/5Z90TBE
108.0°C
96.0°C
90.0°C
85.0°C