13.15 Valve close detection control
This control detects 3-way valve close condition to prevent damage to refrigerant cycle.
Start conditions:
For all connected indoor units, if Indoor intake temperature — indoor piping temperature are between 28.4°F
o
(-2°C) and 35.6°F (2°C) continuously for 5 minutes after compressor ON at first cooling operation.
The first cooling operation is defined as cooling operation is ON for less than 8 minutes after new installation
o
or after pump down.
Control content
During this control, compressor stop, indoor units' Timer LED will blink. ("F91" is indicated at indoor units)
o
Error reset can be done by power supply reset or reset by using remote control.
13.16 Compressor discharge high pressure protection control
This control protect by using high pressure switch during operation.
Start conditions
High pressure switch is activated (from normally close to open) when outdoor operation mode is cooling or
o
heating during compressor running.
Control 1 content
Compressor stop when high pressure switch is opened and restart after high pressure switch closed. If this
o
condition happen 4 times within 30 minutes, "F94" is indicated.
After 30 minutes, counter is reset if this condition does not happen for 4 times.
o
Control 1 stop conditions
Power supply reset
o
Reset by using remote control
o
13.17 Compressor Heater control
Specification:
Power: 30 Watt
o
Voltage: 240 Volt
o
Purpose:
To control compressor crankcase heater operation to melt ice on compressor during heating operation
o
Starting conditions:
When outdoor air temperature ≤ 4°C (39°F) and compressor top temperature ≤ 21°C (70°F)
o
Control contents:
Power supply to compressor heater is ON
o
Cancel conditions:
When outdoor air temperature exceeds by 6°C (43°F) or
o
When compressor top temperature exceeds 26°C (79°F)
o