Fujitsu AIRSTAGE ARUH72TLAV2 Installation Manual page 14

Table of Contents

Advertisement

00 Start/Stop
Emergency
01
stop
External
46
control
02 Forced stop
00 All
Error report
Display only on
47
target
01
central remote
controller
Follow the
Fan setting
setting on
00
when cool-
the remote
49
ing thermo-
controller
stat OFF
01 Stop
00 Mode 0
Switching
01 Mode 1
functions
02 Mode 2
for external
03 Mode 3
inputs and
60
04 Mode 4
external
05 Mode 5
outputs
06 Mode 6
terminals
07 Mode 7
(*2)
08 Mode 8
Auxiliary
00
heater con-
trol 1
Auxiliary
01
heater con-
trol 2
Heat pump
02
prohibition
control
Heater selec-
tion control
03
using outdoor
tempera-
ture 1
Heater selec-
tion control
04
using outdoor
Control
tempera-
switching
61
ture 2
of external
Auxiliary
heaters
heater control
05
by outdoor
temperature 3
Auxiliary heat
06
pump control
Auxiliary heat
pump control
07
by outdoor
temperature 1
Auxiliary heat
pump control
08
by outdoor
temperature 2
Auxiliary heat
pump control
09
by outdoor
temperature 3
00 Setting 0
01 Setting 1
02 Setting 2
03 Setting 3
04 Setting 4
05 Setting 5
06 Setting 6
07 Setting 7
Operating
temperature
08 Setting 8
switching
62
09 Setting 9
of external
10 Setting 10
heaters
11 Setting 11
12 Setting 12
13 Setting 13
14 Setting 14
15 Setting 15
16 Setting 16
17 Setting 17
(Forbidden)
70
00
00 Disable
Standby
01 1 minutes
time for
02 2 minutes
auxiliary
71
equipment
98 98 minutes
operation
99 99 minutes
En-13
Allow an external controller to start
or stop the system, or to perform
an emergency stop.
* If an emergency stop is performed
from an external controller, all refriger-
ant systems will be disabled.
* If forced stop is set, indoor unit stops
by the input to the external input
terminals, and Start/Stop by a remote
controller is restricted.
Change the target for reporting errors.
Errors can either be reported in all lo-
cations, or only on the central remote
controller.
When set to 01, the fan stops
when the thermostat is OFF in
cooling operation. Connection of
the wired remote controller (2-wire
type) and switching its thermistor
are necessary.
• Set this function when connecting
the VRF system to a ventilator,
economizer, humidifi er, or other
external device.
• The connection terminal functions
can be changed depending on
the type of external device. For
details of the connection terminal
functions, see the Design & Tech-
nical Manual.
Sets the control method for the
external heater being used. For
details of the control method, see
the Design & Technical Manual.
• Sets the temperature conditions
when the external heater is ON.
• For the temperature conditions,
see "Temperature conditions
when the external heater is ON".
For a more detailed explana-
tion, see the Design & Technical
Manual.
Sets the standby time until the
auxiliary equipment operation
starts during primary equipment
operation.
00 Disable
Emergency
73
heat
01 Enable
00 1 minutes
Fan delay
01 50 seconds
74
time
02 40 seconds
03 30 seconds
00 Disable
External
heater use
75
in defrost-
01 Enable
ing. (*3)
*1: Auto restart is an emergency function such as for power failure etc.
Do not start and stop the indoor unit by this function in normal operation.
Be sure to operate by the control unit, converter or external input device.
*2: Inappropriate setting may cause an external device malfunction. Confirm whether all
the settings have been performed appropriately according to the installing condition.
*3: When using function number 75, inappropriate heater selection may cause cold air in
defrosting.
Temperature conditions when the external heater is ON/OFF
Temperature (t) = Room temperature - set temperature
00
ON
00
t < -5.4°F (-3°C)
t ≥ -1.8°F (-1°C)
01
t < -3.6°F (-2°C)
t ≥ -1.8°F (-1°C)
02
t < -3.6°F (-2°C)
t ≥ -1.8°F (-1°C)
03
t < -5.4°F (-3°C)
t ≥ -1.8°F (-1°C)
04
t < -7.2°F (-4°C)
t ≥ -1.8°F (-1°C)
05
t < -9.0°F (-5°C)
t ≥ -1.8°F (-1°C)
06
t < -5.4°F (-3°C)
t ≥ -0.9°F (-0.5°C) t ≤ -0.9°F (-0.5°C)
07
t < -3.6°F (-2°C)
t ≥ -0.9°F (-0.5°C)
08
t < -3.6°F (-2°C)
t ≥ -0.9°F (-0.5°C)
09
t < -5.4°F (-3°C)
t ≥ -0.9°F (-0.5°C)
10
t < -7.2°F (-4°C)
t ≥ -0.9°F (-0.5°C)
11
t < -9.0°F (-5°C)
t ≥ -0.9°F (-0.5°C)
12
t < -5.4°F (-3°C)
t ≥ 0°F (0°C)
13
t < -3.6°F (-2°C)
t ≥ 0°F (0°C)
14
t < -3.6°F (-2°C)
t ≥ 0°F (0°C)
15
t < -5.4°F (-3°C)
t ≥ 0°F (0°C)
16
t < -7.2°F (-4°C)
t ≥ 0°F (0°C)
17
t < -9.0°F (-5°C)
t ≥ 0°F (0°C)
Enables or disable of emergency
heat input.
Sets the fan delay time when the
heater is turned off.
Enables or disables the external
heater use in defrosting.
Set value of function: 61
01 to 09
OFF
ON
t ≤ -0.9°F (-0.5°C) t ≥ +0.9°F (+0.5°C)
t ≤ -1.8°F (-1°C)
t ≥ +0.9°F (+0.5°C)
t ≤ -3.6°F (-2°C)
t ≥ +0.9°F (+0.5°C)
t ≤ -5.4°F (-3°C)
t ≥ +0.9°F (+0.5°C)
t ≤ -7.2°F (-4°C)
t ≥ +0.9°F (+0.5°C)
t ≤ -9.0°F (-5°C)
t ≥ +0.9°F (+0.5°C)
t ≥ 0°F (0°C)
t ≤ -1.8°F (-1°C)
t ≥ 0°F (0°C)
t ≤ -3.6°F (-2°C)
t ≥ 0°F (0°C)
t ≤ -5.4°F (-3°C)
t ≥ 0°F (0°C)
t ≤ -7.2°F (-4°C)
t ≥ 0°F (0°C)
t ≤ -9.0°F (-5°C)
t ≥ 0°F (0°C)
t ≤ -0.9°F (-0.5°C) t ≥ -0.9°F (-0.5°C)
t ≤ -1.8°F (-1°C)
t ≥ -0.9°F (-0.5°C)
t ≤ -3.6°F (-2°C)
t ≥ -0.9°F (-0.5°C)
t ≤ -5.4°F (-3°C)
t ≥ -0.9°F (-0.5°C)
t ≤ -7.2°F (-4°C)
t ≥ -0.9°F (-0.5°C)
t ≤ -9.0°F (-5°C)
t ≥ -0.9°F (-0.5°C)
OFF