Setting The Address; Custom Code Setting; Static Pressure Mode; Function Setting - Fujitsu AIRSTAGE ARUH72TLAV2 Installation Manual

Table of Contents

Advertisement

7.1. Setting the address

Manual address setting method
The indoor unit address and the refrigerant circuit
address can also be set up through the wireless
remote controller.
CAUTION
Use an insulated screwdriver to set the DIP
switches.
Setting
Indoor unit address
• Rotary switch [IU AD × 1]
(Factory setting "0")
• Rotary switch [IU AD × 10]
(Factory setting "0")
When connecting multiple indoor units to 1
refrigerant system, set the address at IU AD SW
as shown in the Table A.
Refrigerant circuit address
• Rotary switch [REF AD × 1]
(Factory setting "0")
• Rotary switch [REF AD × 10]
(Factory setting "0")
In the case of multiple refrigerant systems, set
REF AD SW as shown in the Table A for each
refrigerant system.
Set to the same refrigerant circuit address as the
outdoor unit.
• If working in an environ-
Table A
ment where the wireless
remote controller can be
Address
used, the addresses can
also be set using the
Refrigerant
remote controller.
circuit
• If setting the addresses
0
using the wireless
remote controller, set
1
the indoor unit address
2
and refrigerant circuit
address to "00".
3
(For information on set-
4
ting using the wireless
remote controller.)
5
* Do not set the indoor
10
unit address (IU AD
SW) at 64 to 99.
11
It may result in failure.
99

7.2. Custom code setting

• Selecting the custom code prevents the indoor unit mix-up. (figure below)
(Up to 4 codes can be set.)
• Perform the setting for both the indoor unit and the remote controller.
Confusion
Indoor unit
Remote
controller
Custom code setting for indoor unit
Set the DIP switch SET3 SW1, 2, referring to the
figure and table below.
DIP switch "SET3"
DIP switch
ON
OFF
SW
SW
SW
SW
1
2
3
4
For indoor
For refrigerant
circuit address
unit address
IU AD
REF AD
×10
×1
×10
×1
SET3
SET4
Setting
Type of switch
range
Setting example "2"
0 to 63
IU AD × 10
IU AD × 1
Setting example "63"
0 to 99
REF AD × 10 REF AD × 1
Rotary switch
Rotary switch
Address
setting
setting
REF AD SW
IU AD SW
Indoor unit
× 10
× 1
× 10
0
0
0
0
0
1
1
0
0
2
2
0
0
3
3
0
0
4
4
0
0
5
5
0
1
0
10
1
1
1
11
1
9
9
63
6
Code change
A
B
C
D
A
B
C
IU AD
REF AD
×10
×1
×10
×1
SET3
SET4
DIP switch "SET3"
Custom code
A (Factory
SET3
B
C
setting)
SW1
OFF
ON
OFF
SW2
OFF
OFF
ON

7.3. Static pressure mode

If the applicable static pressure does not match the static pressure mode, the static
pressure mode may be changed to another mode manually.
RC AD
Recommended range of external static pressure
ARUH72: 0.20 and 1.20 in WG (50 and 300 Pa)
ARUH96: 0.20 and 1.16 in WG (50 and 290 Pa)
It is necessary to set up a static pressure mode for each usage of static pressure.
Static pressure can be set at site.
Relation between set values and static pressure are as the following table.
• FUNCTION SETTING can be performed with the wired or wireless remote controller.
(The remote controller is optional equipment)
• Refer to the wired or wireless remote controller manual for detailed setting information.
Function
Setting Number
Number
05
SP mode 05
06
SP mode 06
07
SP mode 07
08
SP mode 08
09
SP mode 09
10
SP mode 10
11
SP mode 11
26
12
SP mode 12
28
SP mode 28
29
SP mode 29
30
SP mode 30
31
(Factory setting)
* Please refer to FAN PERFORMANCE CURVE within Design & Technical Data for the
features of each setting.

7.4. Function setting

× 1
• FUNCTION SETTING can be performed with the wired or wireless remote controller.
0
(The remote controller is optional equipment)
1
• Refer to the wired or wireless remote controller manual for detailed setting information.
2
• Refer to "7.1. Setting the address" for indoor unit address and refrigerant circuit address
settings.
3
• Turn the power of the indoor unit ON before starting the setting.
4
* Turning on the power to the indoor units initializes EEV, so make sure the piping air tight
5
test and vacuuming have been conducted before turning on the power.
* Also check again to make sure no wiring mistakes were made before turning on the
power.
0
Function details
1
Function
Function
number
3
Filter indicator
11
interval
Filter indicator
13
action
(Forbidden)
20
(Forbidden)
23
(Forbidden)
24
D
Static pres-
26
sure
RC AD
Cool air
temperature
30
trigger
Heat air
temperature
31
trigger
D
Auto restart
40
(*1)
ON
ON
Cool Air
43
Prevention
CAUTION
Setting Static Pressure
ARUH72
0.20 in WG (50 Pa)
0.24 in WG (60 Pa)
0.28 in WG (70 Pa)
0.32 in WG (80 Pa)
0.36 in WG (90 Pa)
0.40 in WG (100 Pa)
0.44 in WG (110 Pa)
0.48 in WG (120 Pa)
1.12 in WG (280 Pa)
1.16 in WG (290 Pa)
1.20 in WG (300 Pa)
Normal SP
0.60 in WG (150 Pa)
Setting number
Default
Adjust the fi lter cleaning interval noti-
00 Standard
fi cation. If the notifi cation is too early,
01 Longer
change to setting 01. If the notifi cation
02 Shorter
is too late, change to setting 02.
00 Enable
Enable or disable the fi lter indicator.
01 Disable
Setting 02 is for use with a central
Display only on
remote controller.
02
central remote
controller
00
00
00
Refer to 7.3. Static pressure mode
Adjust the cool air trigger temperature.
00 Standard
To lower the trigger temperature,
01 Adjust (1)
use setting 01. To raise the trigger
02 Adjust (2)
temperature, use setting 02.
00 Standard
Adjust the heat air trigger temperature.
To lower the trigger temperature by 6
01 Adjust (1)
degrees C, use setting 01. To lower
02 Adjust (2)
the trigger temperature by 4 degrees
C, use setting 02. To raise the trigger
03 Adjust (3)
temperature, use setting 03.
00 Enable
Enable or disable automatic system
restart after a power outage.
01 Disable
00 Super low
Restrain the cold airfl ow with
making the airfl ow lower when
Follow the
starting heating operation. To
setting on
01
correspond to the ventilation, set
the remote
to 01.
controller
ARUH96
(1.16 in WG (290 Pa))
Details
En-12