Heating Operation And Adjustments; Electric Heat Start-Up - Lennox KGC092 Installation Instructions Manual

Hide thumbs Also See for KGC092:
Table of Contents

Advertisement

5- Turn gas valve switch to OFF. See figure 20. On
Honeywell VR8305Q gas valves, turn the knob on the
gas valve clockwise
figure 21.
6- Wait five (5) minutes to clear out any gas. If you then
smell
gas,
STOP!
gas supplier from a neighbor's phone. Follow the gas
supplier's instructions. If you do not smell gas, go to
the next step.
7- Turn gas valve switch to ON. See figure 20. On
Honeywell VR8305Q gas valves, turn the knob on the
gas valve counterclockwise
force. See figure 21.
8- Close or replace the heat section access panel.
9- Turn on all electrical power to appliance.
10- Set thermostat to desired setting.
11- The ignition sequence will start.
12- If the appliance does not light the first time (gas line
not fully purged), it will attempt up to two more
ignitions before locking out.
13- If lockout occurs, repeat steps 1 through 10.
14- If the appliance will not operate, follow the
instructions "Turning Off Gas to Appliance" and call
your service technician or gas supplier.
Turning Off Gas to Unit
1- If using an electromechanical thermostat, set to the
lowest setting.
2- Before performing any service, turn off all electrical
power to the appliance.
3- Open or remove the heat section access panel.
4- Turn gas valve switch to OFF. On Honeywell
VR8305Q gas valves, turn the knob on the gas valve
clockwise
to "OFF". Do not force.
5- Close or replace the heat section access panel.
WARNING
Danger of explosion. Can cause injury or
death. Do not attempt to light manually.
Unit has a direct spark ignition system.

Heating Operation and Adjustments

(Gas Units)
A-Heating Sequence of Operation
1- On a heating demand the combustion air inducer
starts immediately.
2- Combustion air pressure switch proves inducer
operation. After a 30-second pre-purge, power is
allowed to ignition control. Switch is factory set and
requires no adjustment.
to "OFF". Do not force. See
Immediately
call
your
to "ON". Do not
3- Spark ignitor energizes and gas valve solenoid opens.
4- Spark ignites gas, ignition sensor proves the flame
and combustion continues.
5- If flame is not detected after first ignition trial, ignition
control will repeat steps 3 and 4 two more times
before locking out the gas valve.
6- For troubleshooting purposes, an ignition attempt
after lock out may be re-established manually. Move
thermostat to "OFF" and return thermostat switch to
"HEAT" position.
B-Ignition Control Diagnostic LED's
IGNITION CONTROL HEARTBEAT LED STATUS
LED
Flashes
Slow
Normal operation. No call for heat.
Fast
Normal operation. Call for heat.
Internal control fault OR no power to
Steady Off
control OR Gas Valve Relay Fault.
Steady On Control internal failure.
2
Lockout. Failed to detect or sustain flame.
Prove switch open or closed or rollout
3
switch open.
Limit switch is open and/or limit has
4
opened three times.
Flame sensed but gas valve solenoid
5
not energized.
C-Limit Controls
Limit controls are factory-set and are not adjustable. The
primary limit is located on the blower deck to the right of
blower assembly.
D-Heating Adjustment
Main burners are factory-set and do not require
adjustment.
The following manifold pressures are listed on the gas valve.
Natural Gas Units - Low Fire - 1.6" w.c.
Natural Gas Units - High Fire - 3.7" w.c.
LP Gas Units - Low Fire - 5.5" w.c.
LP Gas Units - High Fire - 10.5" w.c.
Electric Heat Start-Up (KC Units)
Optional electric heat will stage on and cycle with
thermostat demand. Number of stages of electric heat will
vary depending on electric heat assembly. See electric
heat wiring diagram on unit for sequence of operation.
Page 27
TABLE 16
Indicates
(not adjustable)
(not adjustable)

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Kcc092Kgc102Kcc102Kgc120Kcc120Kgc150 ... Show all

Table of Contents