Unit Panels - Carrier PGR5 Owner's Information Manual

15.2+ seer2 2-stage packaged air conditioner and gas furnace system with r-410a refrigerant single and three phase 2-5 nominal tons (sizes 24-60)
Hide thumbs Also See for PGR5:
Table of Contents

Advertisement

PGR5: Owner's Information Manual
WARNING
!
EXPLOSION AND ENVIRONMENTAL HAZARD
Failure to follow this warning could result in personal injury, death or
property damage.
System under pressure. Relieve pressure and recover all refrigerant
before system repair or final unit disposal. Use all service ports and
open all flow-control devices, including solenoid valves.

Unit Panels

After performing any maintenance or service on the unit, be sure all
panels are fastened securely in place to prevent rain from entering unit
cabinet and to prevent disruption of the correct unit airflow pattern.
Combustion Area and Vent System
For proper and safe operation, the unit needs air for combustion and
ventilation. The air openings, on the unit, the air openings to the area in
which the unit is installed, and the spacing around the unit must not be
blocked or obstructed.
The combustion air inlet area and vent hood should be inspected visually
before each heating season. The normal accumulation of dirt, soot, rust,
and scale can result in loss of efficiency and improper performance if
allowed to build up. This inspection should be done by a trained service
person.
WARNING
!
FIRE, EXPLOSION HAZARD
Failure to follow this warning could result in personal injury, death
and/or property damage.
If your unit makes an especially loud noise when the main burners are
ignited, shut down the heating section and call your dealer.
CAUTION
!
BURN HAZARD
Failure to follow this caution may result in personal injury.
Components in heating section may be hot after unit has been started
up. When observing flame, be careful not to get close to or touch
heating components.
Regular Dealer Maintenance (Also see
In addition to the type of routine maintenance you might be willing to
perform, your unit should be inspected regularly by a properly trained
service technician. An inspection (preferably each year) should include
the following:
1. Inspection of all flue product passages-including the burners, heat
exchanger, and flue collector box, Mare sure the burner flames are
blue in color and in proper adjustment. Refer to
flame.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
2. Inspection of all combustion-and ventilation-air passages and
3. Close inspection of all gas pipes leading to and inside of your unit.
4. Inspection and, if required, cleaning of the outdoor and indoor
5. Inspection and, if required, cleaning of the indoor coil condensate
6. Inspection and cleaning of blower wheel housing and motor.
7. Inspection of all supply-air and return-air ducts for leaks,
8. Inspection of the unit base to ensure that no cracks, gaps, etc., exist
9. Inspection of the unit casing for signs of deterioration.
10. Inspection of all electrical wiring and components to assure proper
11. Inspection for leaks in the refrigerant circuit. Pressure check to
12. Operational check of the unit to determine working conditions.
Your servicing dealer may offer an economical service contract that
covers seasonal inspections. Ask for further details.
Complete service instructions can be found in the unit Installation,
Start-up and Service Instructions.
Table
2)
Fig. 8
for burner
9
Fig. 8 – Monoport Burner
openings.
coils.
drain pan.
obstructions, and insulation integrity. Any problems found should
be resolved at this time.
which may cause a hazardous condition.
connection.
determine appropriate refrigerant charge.
Repair or adjustment should be made at this time.
BURNER FLAME
BURNER
MANIFOLD
C99021

Advertisement

Table of Contents
loading

Table of Contents