Viking FREEDOM VK479 Technical Data Manual page 9

Residential horizontal sidewall sprinkler

Advertisement

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Sprinkler Temperature
Classification
Ordinary
Intermediate
Sprinkler Temperature
Classification
Ordinary
Sprinkler Temperature
Classification
Ordinary
Intermediate
Sprinkler Temperature
Classification
Ordinary
The sprinkler temperature rating is stamped on the deflector or flow shaper.
1
The temperature rating is stamped on the sprinkler.
2
Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction.
3
Refer to specific installation standards.
B. Installation Instructions
Viking sprinklers are manufactured and tested to meet the rigid requirements of approving agencies. They are designed to be
installed in accordance with recognized installation standards NFPA 13, NFPA 13R, and NFPA 13D, and any associated TIAs.
Deviation from the standards or any alteration to the sprinklers or cover plate assemblies after they leave the factory including,
but not limited to: painting, plating, coating, or modification, may render the sprinklers inoperative and will automatically nullify the
approval and any guarantee made by Viking.
The use of residential sprinklers may be limited due to occupancy and hazard. Residential fire protection systems must be designed
and installed only by those who are completely familiar with the appropriate standards and codes, and thoroughly experienced in
fire protection design, hydraulic calculations, and sprinkler system installation.
Before installation, be sure to have the appropriate sprinkler model and style, with the correct K-Factor, temperature rating, and
response characteristics. Viking residential sprinklers must be installed after the piping is in place to prevent mechanical damage.
Keep sprinklers with protective caps or bulb shields contained within the caps or shields during installation and testing, and any time
the sprinkler is shipped or handled.
1a. For frame-style sprinklers, install escutcheon (if used), which is designed to thread onto the external threads of the sprinkler*.
*Refer to the appropriate sprinkler technical data page to determine approved escutcheons for use with specific sprinkler models.
1b. For flush and concealed style sprinklers: Cut the sprinkler nipple so that the ½" or 3/4" (15 mm or 20 mm) NPT** outlet of the
reducing coupling is at the desired location and centered in the opening** in the ceiling or wall.
**Size depends on the sprinkler model used. Refer to appropriate sprinkler data page.
Form No. F_080190
18.10.25
TECHNICAL DATA
TABLE 1: RESIDENTIAL SPRINKLER TEMPERATURE RATINGS
Sprinkler Nominal
Temperature Rating
Residential Glass Bulb Style Sprinklers
155 °F (68 °C)
175 °F (79 °C)
Sprinkler Nominal Temperature
Rating (Fusing Point)
Residential Fusible Element Style Sprinklers
165 °F (74 °C)
Sprinkler Nominal Temperature
Rating (Fusing Point)
Residential Flush Style Sprinklers
165 °F (74 °C)
220 °F (104 °C)
Sprinkler Nominal Temperature
Rating (Fusing Point)
Residential Concealed Style Sprinklers
135 °F (57 °C)
, 140 °F (60 °C)
1
155 °F (68 °C)
, or 165 °F (74 °C)
1
Rev 16.1.P65
Maximum Ambient
Ceiling Temperature
1
100 °F (38 °C)
150 °F (65 °C)
1
Maximum Ambient
Ceiling Temperature
100 °F (38 °C)
150 °F (65 °C)
Maximum Ambient
Ceiling Temperature
,
2
100 °F (38 °C)
1
Footnotes
Sprinkler RES2
FREEDOM
RESIDENTIAL
®
SPRINKLER
INSTALLATION GUIDE
Bulb Color
3
Red
Yellow
Maximum Ambient
Ceiling Temperature
3
100 °F (38 °C)
Temperature
Identification Stamp
3
On Cover or
Sprinkler Inlet (VK476)
On Cover
Cover Plate Temperature
Rating
3
135 °F (57 °C)