Viking FREEDOM VK479 Technical Data Manual page 22

Residential horizontal sidewall sprinkler

Advertisement

Sprinkler RES15
FREEDOM
RESIDENTIAL
®
SPRINKLER
TECHNICAL DATA
INSTALLATION GUIDE
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
NOTE: The dimensions shown are intended to apply to residential sprinklers installed in ceilings above fireplaces used to burn
products that cause elevated temperatures at or near the ceiling in areas surrounding the fireplace. The recommendations should
not be construed to apply to decorative non-opening fireplaces such as gas fire units that will not cause elevated temperatures
at the ceiling.
Top View
3'-0" (.91 m)
3'-0" (.91 m)
Front View
Sprinklers near an open hearth fireplace must be located outside of the shaded area or be intermediate degree rated.
Top View
3'-0" (.91 m)
Side of fireplace
Front of fireplace
5'-0" (1.5 m)
Front View
Sprinklers near a recessed hearth fireplace must be located outside of the shaded area [at least 3'-0" (.91 m)] from the side
of a recessed fireplace and at least 5'-0" (1.5 m) from the front) or be intermediate degree rated.
Form No. F_080190
18.10.25
Rev 16.1.P65