HP HPE SimpliVity 325 Getting Started Manual page 18

Gen10 server
Table of Contents

Advertisement

Specification
Rated input power (W)
Rated input power (BTUs per hour)
Power supply output
Rated steady-state power (W)
Maximum peak power (W)
Maximum peak power
WARNING: To reduce the risk of electric shock or energy hazards:
This equipment must be installed by trained service personnel.
Connect the equipment to a reliably grounded secondary circuit source. A secondary circuit has no direct
connection to a primary circuit and derives its power from a transformer, converter, or equivalent isolation
device.
The branch circuit overcurrent protection must be rated 27 A.
CAUTION: This equipment is designed to permit the connection of the earthed conductor of the DC supply circuit
to the earthing conductor at the equipment.
If this connection is made, all of the following must be met:
This equipment must be connected directly to the DC supply system earthing electrode conductor or to a
bonding jumper from an earthing terminal bar or bus to which the DC supply system earthing electrode
conductor is connected.
This equipment must be located in the same immediate area (such as adjacent cabinets) as any other
equipment that has a connection between the earthed conductor of the same DC supply circuit and the earthing
conductor, and also the point of earthing of the DC system. The DC system must be earthed elsewhere.
The DC supply source is to be located within the same premises as the equipment.
Switching or disconnecting devices must not be in the earthed circuit conductor between the DC source and the
point of connection of the earthing electrode conductor.
18
Specifications
Value
874 W at -40 VDC input
865 W at -48 VDC input, nominal input
854 W at -72 VDC input
2983 at -40 VDC input
2951 at -48 VDC input, nominal input
2912 at -72 VDC input
800 W at -40 VDC to -72 VDC
800 W at -40 VDC to -72 VDC
800 W at -40 VDC to -72 VDC input

Advertisement

Table of Contents
loading

Table of Contents