Wiring; Terminal Connection Diagram (When Source Logic Is Selected) - Mitsubishi Electric FR-E540 K-EC Series Instruction Manual

Large capacity inverter
Hide thumbs Also See for FR-E540 K-EC Series:
Table of Contents

Advertisement

2.2 Wiring

2.2 Wiring

2.2.1 Terminal connection diagram (when source logic is selected)

3-phase 400V power input
NFB
MC
3-phase AC
power supply
24VDC power output and
contact input common
Forward rotation start
Reverse rotation start
Multi-speed selection
Output stop
External transistor common and
24VDC power output common
Control input signals
(no voltage input allowed)
Frequency setting signals (analog)
3
(Note 1)
2
Frequency
setting
1
potentiometer
Current input( )
1/2W1k
4 to 20mADC(+)
Note: 1. If the potentiometer is to be operated often, use a 2W1k potentiometer.
2. Terminals 5, SD and SE are isolated.
3. Terminals SD and 5 are common terminals. Do not earth them to the
ground.
4. When terminals PC-SD are used as a 24VDC power supply, be careful not
to short these terminals. If they are shorted, the inverter will be damaged.
L
1
L
2
L
3
PC
Note 4
STF
STR
High
RH
Middle
RM
Low
RL
MRS
Reset
RES
SD
Note 3
Note 2
10(+5V)
0 to 5VDC
2
Selected
0 to 10VDC
5(Analog common)
Note 3
Note 2
4(4 to 20mADC)
PU connector
(RS-485)
13
INSTALLATION AND WIRING
Motor
U
V
W
P1
Jumper
Remove this jumper when
+
using the optional power-factor
PR
improving DC reactor.
Brake resistor connection
A
B
Alarm
detection
C
RUN
Running
FU
Frequency detection
SE
Open collector
output common)
AM
(+)
Analog signal output
(0 to 10VDC)
5
( )
Earth(Ground)
Main circuit terminal
Control circuit input terminal
Control circuit output terminal
IM
Earth(Ground)
Open
collector outputs