Unit installation

6.3.5 To provide drainage

General guidelines
Installer reference guide
30
NOTICE
Do NOT use nippers to remove the pipe port cover, as this would damage the front
grille.
Make sure condensation water can be evacuated properly. This involves:
General guidelines
Connecting the drain piping to the indoor unit
Checking for water leaks
Pipe length. Keep drain piping as short as possible.
Pipe size. If drain hose extension or embedded drain piping is required, use
appropriate parts that match the hose front end.
NOTICE
Install the drain hose with a downward slope.
Traps are NOT permitted.
Do NOT put the end of the hose in water.
Drain hose extension. To extend the drain hose, use a field supplied hose with
inner Ø16 mm. Do NOT forget to use a heat insulation tube on the indoor section
of the extension hose.
a
a Drain hose supplied with the indoor unit
b Heat insulation tube (field supply)
c Extension drain hose
a
b
c
FTXP20~35N5V1B + ATXP20~35N5V1B
Split system air conditioners
4P519439-20U – 2022.09