Terminations/Spark Arrestor
The fireplace system must be terminated with
the listed round top or chase terminations. In
any case, refer to the installation instructions
supplied with the termination.
CAUTION: Do not seal open-
ings on the rooftop flashing. Fol-
low the installation instructions
provided with the termination
being used.
Stainless
Inner Flue
Pipe
Secure
Termination
to Outer
f i r e - p a r t s . c o m
Pipe with 3
Screws
Overlap
Shingles (Top
and Sides of
Flashing Base)
Figure 17 - Termination
CHASE INSTALLATIONS
Instructions for chase installations are
included with the chase style termination
chosen. In a multiple chase installation, be
sure to provide adequate distance between
terminations to prevent smoke spillage from
one termination to another. We suggest that
terminations be separated at least 24", center
to center and stacked at a vertical height dif-
ference of 18" (see Figure 18).
Note: If a decorative shroud is to be installed,
contact the manufacturer for specifications.
12
VENTING INSTALLATION
Continued
RLT-12D
Level of
Flue Gas
Outlet
Waterproof
Caulking
Storm
Collar
Flashing
Underlap
Shingles
www.SuperiorFireplaces.US.com
24" Min.
24" Min.
Figure 18 - Multiple Chase Installation
10 FOOT RULE
All flue gas outlet chimney terminations must
extend a minimum of 3 feet in height above
the highest point where it passes through
the roof and must be at least 2 feet above
the highest point of the roof that is within a
horizontal distance of 10 feet (see Figure 19).
10'
2' Min.
Figure 19 - 10 Foot Rule
FINISHING FIREPLACE
Combustible materials, such as wallboard,
gypsum board, sheet rock, drywall, plywood,
etc. may make direct contact with sides and top
around the fireplace face. It is important that
combustible materials do not overlap the face
itself. Brick, glass, tile or other noncombustible
materials may overlap the front face provided
they do not obstruct essential openings like
louvered slots or any other opening. When
overlapping with a noncombustible facing
material, use only noncombustible mortar or
adhesive.
Level of
Flue Gas
Outlet
10'
3' Min.
2' Min.
127011-01A
18"
Min.
Typ.
3' Min.