Toshiba VF-NC3C Instruction Manual page 28

Advertisement

FOR REFERENCES ONLY
[Example of how to adjustment the FM terminal frequency meter]
*
Use the meter's adjustment screw to pre-adjust zero-point.
Operation panel action
-
MODE
+
MODE
MODE
 Adjusting the meter in inverter stop state
 Adjustment of output current (=1)
If, when adjusting the meter for output current, there are large fluctuations in data during adjustment,
making adjustment difficult, the meter can be adjusted in inverter stop state.
When setting  to  for fixed output 1 (output current 100% equivalent), a signal of absolute
values will be output (inverter's rated current = 100%). In this state, adjust the meter with the  (Meter
adjustment) parameter.
Similarly, if you set  to  for fixed output 2 (output current 50% equivalent), a signal that is sent
out when half the inverter's rated current is flowing will be output through the FM terminal.
After meter adjustment is ended, set  to  (output current).
 Other adjustments ( = ,  - , , , )
 = : When fixed output 3 (other than the output current) is set, a signal of the the value for
other monitors is fixed at the following values and output through the FM terminal.
100% standard value for each item is the following:
=0, 2, 12
=3, 4
=13
=18
VFNC3C ENGLISH MANUAL
LED display
Displays the output frequency.
. 
(When standard monitor display selection  is set to )
The first basic parameter "" (history function) is displayed.


Turn the setting dial to select .
Operation frequency can be read by pressing the center of the setting
. 
dial.
Turn the setting dial to adjust the meter.
Note that the meter's indicator changes at this time, but the inverter's
display (monitor) does not change.
. 
 ⇔
Press the center of the setting dial to save the meter's calibrations.
 and the frequency are displayed alternately.

The display returns to its original indications.
. 
(When standard monitor display selection  is set to 
[Operation frequency])
: Maximum frequency (h)
: 1.5 times of rated voltage
: Maximum input value (5V, 10V, or 20mA)
: Maximum value (1000)
C-15