Models And General Specifications Of I/O Modules; General Specifications - YASKAWA MEMOCON GL120 User Manual

Table of Contents

Advertisement

2 Models and General Specifications of I/O Modules

2.1

General Specifications

Environmental
Conditions
Mechanical
Operating
Conditions
Electrical
Operating
Conditions
Installation
Requirements
This section gives the general specifications of I/O Modules.
Table 2.1 General Specifications
Item
Ambient Operating Temperature
Ambient Storage Temperature
Ambient Operating Humidity
Ambient Storage Humidity
Pollution Level
Corrosive Gas
Operating Altitude
Vibration Shock
Shock Resistance
Noise Resistance
Ground
Configuration
Cooling Method
Mass
External Dimensions
0 °C to 60 °C
-25 C° to 85 °C (excluding battery)
30 % to 95 % RH (with no condensation)
5 % to 95 % RH (with no condensation)
Pollution level 1 (according to JIS B3502)
No corrosive gas
Less than 2,000 m above sea level
10 to 57 Hz with half-amplitude of 0.075mm
57 to 150 Hz with fixed acceleration of 9.8 m/s
10 sweep times each in X, Y, and Z directions
(sweep time: 1 octave/min) (according to JIS B3502)
Peak acceleration of 147 m/s
and Z directions (according to JIS B3502)
1,500 V in either normal or common mode with pulse
widths of 100 ns and 1 µs and rise time of 1 ns (with
impulse noise simulator) (according to JIS B3502)
Ground to 100 Ω or less
Building-block, wall-mounted, or DIN track mounted
Natural cooling
See specifications for individual I/O Modules.
See specifications for individual I/O Modules.