Johnson Controls METASYS NU-XBN101-0 Technical Manual page 28

Multiplex binary module
Table of Contents

Advertisement

N2 Bus Connection
Identification
Code Association to
Graphics and Help
Screens
Flags
28 Point Multiplex Modules—Multiplex Binary
Expanded ID
Enter any valid 0-24 character string.
NC Trunk Number
A check must be made that the port selected is defined as an N2 trunk.
Device Address
(0-255) Enter the N2 address assigned to the XBN. The address must
not be assigned to any other device on this N2 trunk.
Poll Priority
(0-3) Enter the priority that this device should be polled at.
Device Type
(1-3) Enter which type of Point Multiplex Module: 1 = XBN,
2 = XRM, 3 = XRL/XRE.
Graphic Symbol
If a graphic has been composed to associate with this object, enter the
number of the graphic (0-32767). Zero means no graphic is associated
with this object.
Operating Instr.
When "Help" is selected for this object, a notepad appears containing
user-modifiable operator instructions. Enter the number (0-32767) to
reference the desired notepad. Zero means no operator instructions
will be associated with this object.
Auto Dialout
(Y or N) Select whether Critical 4 reports from this object will force
an auto dialout if a remote Operator Workstation is on a dial-up link.