Johnson Controls METASYS NU-XBN101-0 Technical Manual page 17

Multiplex binary module
Table of Contents

Advertisement

Binary Input Wired Across the Load
A binary input wired across the load (Figure 11) is a typical wiring
configuration and requires no alteration to the circuit. Set the XBN mode
switch to voltage. Examples of these loads include:
fan motors
pumps
lights
compressors
H
Control
Switch
Figure 11: Wiring Across the Load
For applications normally wired across the load, make sure you don't wire
across the control switch (Figure 12).
H
Control
Switch
Figure 12: Incorrect Wiring Method (Across Control Switch)
120 V
N
M
120 V
M
Point Multiplex Modules—Multiplex Binary
xbn9
N
xbn10
17