Table 3. Component selection for TWA heat pump units 6–20 tons
Unit
TWA0724*A
Refrigerant ckts
1
Minimum step (tons)
6
Tube diameter (in.)
Horizontal (& drops)
1 1/8
Vertical (up)
7/8
Schraeder valve
(a)
Access port 3/ckt
w/core
Tube diameter (in.)
1/2
(b)
Filter drier
DHY01608
Sight glass 1/ckt
GLS00853
Schraeder valve
(a)
Access port 2/ckt
w/core
Additional oil charge
0 oz
Notes:
1.
On Access ports 2/ or 3/ckt: Valve body VAL01483, valve core COR00006, valve cap CAP00072
2.
On Filter drier: The heat pump products require two filters and two check valves: one set-oriented for liquid in the cooling direction, and one set-oriented for liquid in the
heating direction. For units with line lengths in excess of 80 ft, the included filters must be removed and filters from the table must be installed close to the air handler. See