PRODUCT DESIGN
Horizontal terminations should be as shown in the follow-
ing figure. Refer to Vent/Flue Pipe and Combustion Pipe -
Termination Location section in this manual or the installa-
tion instructions for location restrictions. A 2 3/8" diameter
wall penetration is required for 2" diameter pipe while a
3 1/2" diameter hole is required for 3" diameter pipe. To
secure the pipe passing through the wall and prohibit dam-
age to piping connections, a coupling should be installed
on either side of the wall and solvent cemented to a pipe
connecting the two couplings. The pipe length should be
the wall thickness plus the depth of the socket fittings to be
installed on the inside and outside of the wall. The wall pen-
etration should be sealed with silicone caulking material.
3" MINIMUM
24" MAXIMUM
3" MINIMUM
24" MAXIMUM
90°
MEDIUM RADIUS
ELBOW
SCREEN
90% Furnace Standard Horizontal Terminations
(Dual Pipe)
24" MAXIMUM
AIR
INTAKE
90% Furnace Alternate Horizontal Vent Termination
(Dual Pipe)
52
Rev. 1
12" MINIMUM
VENT/FLUE
TEE
COMBUSTION
AIR INTAKE
12" MINIMUM
12" MINIMUM
VENT
90°
MEDIUM
RADIUS
ELBOW
12" MINIMUM
24" MAXIMUM
3" MINIMUM
SCREEN
12" MINIMUM
3" MINIMUM
24" MAXIMUM
SUPPORT
STRAPS
COMBUSTION
AIR INTAKE
90°
SCREEN
MEDIUM
RADIUS
ELBOWS
90% Furnace Standard Horizontal Terminations
Above Anticipated Snow Level
(Dual Pipe)
MEDIUM RADIUS
12" MINIMUM
SCREEN
24" MAXIMUM
12" MINIMUM ABOVE
HIGHEST ANTICIPATED
SNOW LEVEL
90% Furnace Alternate Horizontal Terminations
Above Anticipated Snow Level
(Dual Pipe)
In a basement installation, the pipes may be run between
the joist spaces. If the pipes must go below the joist and
then up into the last joist space to penetrate the header, two
45° elbows should be used to reach the header rather than
two 90° elbows.
Vent/Intake Terminations for Installation of Multiple
Direct Vent Furnaces (90% Furnaces Only)
If more than one direct vent furnace is to be installed verti-
cally through a common roof top, maintain the same mini-
mum clearances between the exhaust vent and air intake
terminations of adjacent units as with the exhaust vent and
air intake terminations of a single unit.
12" MINIMUM
VENT/FLUE
TEE
12" MINIMUM ABOVE
HIGHEST ANTICIPATED
12" MINIMUM ABOVE
SNOW LEVEL
HIGHEST ANTICIPATED
SNOW LEVEL
90°
VENT
ELBOWS
24" MAXIMUM
3" MINIMUM
AIR INTAKE