Delta M125HV-113 Quick Installation Manual

Dc wiring box

Advertisement

Quick Links

M125HV_113 user manual
For more instruction and specification, please scan QR-code to see user manual.
> Inverter > M125HV_113 Operation and Installation Manual
https://mydeltasolar.deltaww.com/?p=product_manual
Descriptions of Components
Object
Qty
1
DC Wiring Box
1
2
Quick Installation Guide
1
3
M5 Hex Nut
5
4
M8 Hex Nut
3
5
M12 Hex Nut and Washer
3 set
Installation Steps
Wall
1
Step
Step
Mount the inverter
DC wiring box Installation
After mounting M125HV, please open the front cover of the DC wiring box before install the wiring box on the inverter.
* Screw torque: 4.4 N•m
Pass through the DC cable from M125HV to DC wiring box, Use 4 M5 hex nut to fix the DC wiring box on the
M125HV inverter. (M5 Nut torque: 3.0 N•m)
Use M8 hex nut to tighten the cable on terminal.
Quick Installation Guide
DC Wiring Box for M125HV_113
Description
For DC cable wiring
The Instruction to provide the information of safety,
Installation and specification.
To fix DC wiring box at the bottom of the inverter
To fix DC cable from M125HV inverter
For DC cable wiring
Wall
2
3
Step
Install the DC wiring box
Start DC & AC cabling
* M8 Nut torque: 14.7 N•m
5013294300
Layout
x3
Electrical Installation for DC Wiring
- PV array converts sunlight into electric power with high DC voltage and high DC current which can cause
dangerous electrical shock hazard!
- Use an opaque material to cover the PV array before wiring or cabling.
- Ensure the correct polarities are connected when DC cabling is applied.
- It is forbidden to open both doors at the same time.
- The risk of electric shock and fire exists because of high DC and AC voltages.
- Only PV modules that are listed with system voltage under 1600V are permitted for use.
- Inverter warranty void if the DC input voltage exceeds 1600 Vdc.
- Ensure the DC switch is placed in the "OFF" position, and the PV array is disconnected when doing DC cabling.
Wall
- In order not to damage the components in the inverter, don't repeat to change the status of DC Switch quickly,
the correct operation is waiting for the LED display show "green off and yellow flash" (No DC) or turn on the
switch after 5 minutes later.
- In order not to damage the components in the inverter, ensure the correct conductor is connected to the
appropriate DC terminal on the inverter.
- Ensure the DC conductors used are sized to the correct ampacity per NEC or other local code.
Below is the procedure for preparing the DC conductors for connection to the DC terminals:
• It is important to choose the proper size for DC cable.
• The cross-sectional area for each DC conductor is 50~300 mm
• The maximum width of each terminal lugs should be within 34 mm, the diameter of screw hole should be
larger than Φ12.5 mm.
• Terminal can use for Cu lug (Tin plated).
Conductor cross-section:
Cu: 50 ~ 300 mm
Al: 120 ~ 300 mm
DC Terminal (tin-plated)
Conductor Compatible Lug
Cu(Tin-Plated)
Cu(Nickel-Plated)
Cu
Pure Cu
Stainless steel
Aluminum (Tin-Plated)*
Al
Bi-metal*
* It is recommended to apply electrical grease before fitting wire conductor into terminal lug for best protection.
Prior to installing conductors on terminal complete the following procedure to make terminals ready for connections.
For each of the DC terminals (PV+ / PV-):
Tighten/Lose nuts with 19 mm socket. If an electric socket is utilized insure the torque setting is low enough to
NOT OVER-TORQUE the screw. Once nut bottoms out, do not turn it any further.
Extreme temperature rise at the clamping point
If the contact resistance between the aluminum conductor and clamping point is toohigh, the
clamping point can become very hot and even catch fire in extreme cases.
To ensure a safe and reliable contact, always perform the following work steps:
Please select the Al wire size according to rules due to lower conductivity of Al.
Keep the installation location as free as possible from moisture or corrosive atmospheres.
Connect the aluminum cables quickly.
Tighten the clamping screw in the clamping body with the maximum permissible tightening torque.
After inserting conductor,
torque terminal nut by 45 N • m
The thread surface of
the washer must contact
to hex nut.
Up to 28.9 mm trade size gland
The figure above illustrates the location of the DC conduit entry and connections to the DC terminal block:
- Ensure the correct conductor is connected to the appropriate terminal.
- After conductor is inserted, use M12 nuts to tight PV+/PV- terminal with a torque of 45 N • m.
NO.
1
2
3
4
DANGER : ELECTRICAL HAZARD!!
DANGER!
WARNING !
CAUTION: DC SWITCH ON/OFF !
CAUTION: WRONG AC WIRING !
2
for Cu. (120~300 mm
PV+
2
PV-
2
The working temperature of power cable should be at least 90°C.
NOTICE
DC terminal
Bottom DC entry
PV- PV+
Component
DC terminal
28.9 mm gland for DC Wiring
DC switch
Fuse holder
2
for Al)
outer
jacket
Φ12.5 mm
<34 mm
<32 mm

Advertisement

loading

Summary of Contents for Delta M125HV-113

  • Page 1 5013294300 Layout Quick Installation Guide DC Wiring Box for M125HV_113 M125HV_113 user manual ① Component For more instruction and specification, please scan QR-code to see user manual. DC terminal > Inverter > M125HV_113 Operation and Installation Manual https://mydeltasolar.deltaww.com/?p=product_manual 28.9 mm gland for DC Wiring DC switch Descriptions of Components Fuse holder...
  • Page 2 內部架構 快速安裝指南 M125HV_113 直流配線箱 M125HV_113 操作手冊 ① 部件 如需更多說明和規格,請掃描二維碼查看操作手冊。 直流端子 > 變流器 > M125HV_113 操作手冊 https://mydeltasolar.deltaww.com/?p=product_manual 28.9 mm 直流輸入接頭 直流開關 產品概述 保險絲 ② ③ ④ 直流配線安裝 ① ② ③ ④ ⑤ 危險:觸電危險!! - 太陽能串列將太陽能轉換成高壓直流形式,此高壓有可能造成觸電危險。 物件 數量 描述 - 配線前請使用非透明物質將太陽能串列遮蓋起來。 直流配線箱 用於直流配線...