Advertisement

Quick Links

The power behind competitiveness
Delta InfraSuite Precision Cooling
CoolDoor
User Manual
www.deltapowersolutions.com

Advertisement

Table of Contents
loading

Summary of Contents for Delta CoolDoor

  • Page 1 The power behind competitiveness Delta InfraSuite Precision Cooling CoolDoor User Manual www.deltapowersolutions.com...
  • Page 2 Failure to heed these instructions and warnings will void the warranty. Copyright © 2021 by Delta Electronics Inc. All Rights Reserved. All rights of this User Manual (“Manual”), including but not limited to the contents, information, and figures are solely owned and reserved by Delta Electronics Inc.
  • Page 3: Table Of Contents

    3.7 External Piping ...................... 26 3.8 CoolDoor Water Side Installation Components ............ 27 3.8.1 CoolDoor Control Ball Valve (Standard Accessory) ........27 3.8.2 Pressure Independent Control Valve (Optional Accessory) ....... 29 3.8.3 Leakage Cut Off Valve (Optional Accessory) ..........30...
  • Page 4 Chapter 8 : Maintenance & Cleaning ................... 73 8.1 Component Maintenance ..................73 8.2 Component Replacement ..................74 8.3 Quarterly Maintenance ..................76 Chapter 9 : MODBUS Table ....................78 Appendix 1 : Specifications ....................80 Appendix 2 : Warranty ......................82 InfraSuite - CoolDoor...
  • Page 5: Chapter 1 : Guide For Safe Operation

    The unit contains moving components. Be careful to keep it away from arms, legs, hair, • clothes and jewelry, so as to avoid any danger. When the CoolDoor, which has a certain weight, is installed in an empty rack, the • counterweight in the rack should be appropriately increased to avoid tipping due to...
  • Page 6: Installation Instructions

    All electrical work or procedures must comply with local, state, and national electrical standards and regulations. Except for the power supply, do not make any other electrical connections with this device. InfraSuite - CoolDoor...
  • Page 7: Nameplate Information

    Nameplate Information Puduct Rear Door Cooling Model No. RWC050D0AK00B8 Unit Name Cool Door 50kW Power Supply 1~ 200-240Vac Max 4.2A 50/60Hz 4.5A 5.5A Fan Motor , FLA/HP(Q'ty) 0.9A / 0.242HP(4) Rated Air Volume (Ref.) 4016 CFM (113.7 CMM) Max Allowable Inlet Pressure 142 psig (10 kg/cm Net Weight 216 lb (98 kg)
  • Page 8: Product Introduction

    Product Introduction The CoolDoor precision cooling device (chilled water type) is an air conditioning product that must be installed in combination with an IT rack or any standard rack, and is capable of quickly removing and outputting hot air from the racks. It can achieve precise control through the internal heat exchanger, EC fan, chilled water ball valve, and PLC control.
  • Page 9 Hot aisle expansion • Disassembly and installation can be performed through the side panels of the CoolDoor to achieve sharing of the hot aisle and partial backup for adjacent CoolDoor- Rack systems. Lockable access door • The CoolDoor includes a locking mechanism to prevent unrelated personnel from opening it.
  • Page 10: Dimensions

    Dimensions Model no. 1968 mm 660.4mm 373mm 374.5mm 176mm 355mm RWC050D0AK00B8 160mm 143mm 22mm 160mm 158mm 80mm InfraSuite - CoolDoor...
  • Page 11: Design Capacities

    The range of design conditions shown in the above table will vary with the user's design ability, water volume, and different return air temperatures. It is recommended that you contact Delta service personnel and provide them with detailed calculation parameters in the design.
  • Page 12: Chapter 2 : Introduction

    Chapter 2 : Introduction Packing List InfraSuite - CoolDoor...
  • Page 13 Description Quantity Standard Part CoolDoor Cooling Unit User Manual Door Key Ball Valve Body Ball Valve Actuator Pressure Independent Control Valve Electric Shut-off Valve Remote Sensor...
  • Page 14: Optional Accessories

    • going through a balancing valve. Cut off valve: Can block the waterway when the system leaks. • Flow meter: Can monitor the flow of the CoolDoor, and can be used for TAB • adjustment. Appearance (Figure 2-1: Outer Dimensions)
  • Page 15: Component Identification

    Component Identification External (Figure 2-2: External View) Description Description Display Panel Upper Signal Cable Inlet Connect Duct Rear Door Handle Control Panel Cover Hot Aisle Cover Bottom Signal Cable Inlet Upper Water Pipe Inlet Bottom Water Pipe Inlet Power Cable Inlet Status LED...
  • Page 16 Internal (Figure 2-3: Internal View) Description Description Outlet Pipe Control Panel Inlet Pipe Supply Air Temperature Sensor Return Air Temperature Sensor Air Pressure Detector Coil Protector Electronic Panel Coil InfraSuite - CoolDoor...
  • Page 17: Piping System

    Piping System (Figure 2-4: Piping System) Description Description Lower inlet connector Inlet water temperature sensor Lower outlet connector Outlet water temperature sensor Upper inlet connector Coil Upper outlet connector Air Vent...
  • Page 18: Chapter 3 : Installation

    Inspect the rated values of each unit and make sure they have been properly grounded. One branch circuit or power distribution device can only be connected with one cooling unit. InfraSuite - CoolDoor...
  • Page 19: Space Reservation

    Space Reservation To facilitate maintenance and operation, and to promote air flow circulation, leave clearance in the equipment's surroundings. 1. To ensure normal operation of the indoor unit, whenever possible, select a spacious room to install the indoor unit in. It is advised to leave at least 2.5 feet on the rear where the door opens to facilitate wiring and piping, as is shown in Figure 3-1.
  • Page 20: Handling

    4. When relocating this equipment, mind the height of the center of gravity. Transport requires at least two people at the same time, in order to ensure safety. (Figure 3-3: Transport with A Forklift) (Figure 3-4: Transport with A Hoist) InfraSuite - CoolDoor...
  • Page 21: Positioning

    3.4.1 Remove the Rack Door Panel If Delta's dedicated rack model MSR1110 is used, you must remove the rear door • before installing the CoolDoor extension frame. Follow the steps below: 1. If the back door is locked, use the attached key to open it.
  • Page 22: Install Cooldoor Connect Duct

    3.4.2 Install CoolDoor Connect Duct Use M4 screws (8 PCS) and M6 screws (4 PCS) packed in the accessory bag to fix • the extension frame to the rack Grounding Wire (Figure 3-6: Fix Position) InfraSuite - CoolDoor...
  • Page 23: Hang Cooldoor On Connect Duct

    3.4.3 Hang CoolDoor on Connect Duct Use a lifting harness to stand up the CoolDoor, then align the three hinges to hang it • above Connect Duct (Figure 3-7: Insert to Hinge)
  • Page 24: Holing

    The outer layer of the pipe is covered with an insulation layer to reduce damage from external collisions or unintentional condensation that can lead to dripping. Leave a margin of about 13mm for the hole diameter. The figure below shows the position of the power cable and signal cable at the door. InfraSuite - CoolDoor...
  • Page 25: Piping Installation Size

    Piping Installation Size Description Inlet Pipe 1B-NPT-male 1 1/4B-NPT-male Outlet Pipe 1B-NPT-male 1 1/4B-NPT-male (Figure 3-8: Pipe thread)
  • Page 26: External Piping

    External Piping (Figure 3-9: External Piping) As shown in Figure 3-9, the door of the CoolDoor will open and close during application. Therefore, pipes must be fitted at the water inlet and outlet. Note that the soft tubes and connections must be able to have acceptable rotation. The standard of connection is a screw cross-over joint, or an optional quick joint.
  • Page 27: Cooldoor Water Side Installation Components

    The valve is usually installed in the chilled water supply channel on site. At the end of • the soft tube of the water outlet of the CoolDoor, the customer supply channel is installed under the raised floor. Power wiring is performed according to the terminal wire colors, as shown in Figure 3- •...
  • Page 28 The valve should be installed in accordance with standard piping and local HVAC • codes. If necessary, it is recommended that you install a filter at the inlet of the CoolDoor. For the location of the ball valve connector, please refer to Figure 3-11. • InfraSuite - CoolDoor...
  • Page 29: Pressure Independent Control Valve (Optional Accessory)

    The valve is usually installed in the chilled water supply channel on site. At the end of • the soft tube of the water outlet of the CoolDoor, the customer supply channel is installed under the raised floor. Power wiring is performed according to the terminal wire colors, as shown in Figure 3- •...
  • Page 30: Leakage Cut Off Valve (Optional Accessory)

    The valve is usually installed in the chilled water supply pipeline on site, at the inlet of • the soft tube at the water inlet of the CoolDoor, and the customer supply pipeline is installed under the raised floor. Power wiring is performed according to the terminal wire colors, as shown in Figure 3- •...
  • Page 31: Flow Meter (Optional Accessory)

    The flow meter is usually installed in the chilled water supply pipeline on site, at the • inlet of the soft tube at the water inlet of the CoolDoor, and the customer supply pipeline is installed under the raised floor. When installing the flow meter, maintain a distance of 5 times the pipe diameter from the front pipe.
  • Page 32: Remote Sensor (Optional Accessory)

    It is recommended that you install a remote sensor at the entrance of the server rack • to monitor the environmental dew point temperature so that the CoolDoor will give an alarm when the risk of condensation is high. It is recommended that you install a remote sensor every 5 to 7 racks.
  • Page 33 (Figure 3-16: Leakage Detection Sensor & Connector) The recommended layout of the leakage detection sensor is shown in Figure 3-17. Method 1: Route it around the CoolDoor and rack. Method 2: Place it under the elevated floor. It can be fixed with suitable non-conductive glue (silicone glue).
  • Page 34: Water Quality Requirements

    In order to ensure the long-term and reliable operation of the CoolDoor, water quality control must be carried out for the piping system of the CoolDoor to prevent small particles from damaging the O-rings of the components, which can lead to poor sealing, the ball valve components being unable to be operated due to deposits, or even a decrease in the heat transfer effect due to the fouling of the inner surface of the coil.
  • Page 35: Chapter 4 : Wiring

    Chapter 4 : Wiring Connect the Power Cables Before connecting, be sure to disconnect the external power supply and use an electric • meter to confirm that the power is off. The input power must meet the rating shown on the equipment nameplate. •...
  • Page 36: Connect The Signal Cables

    Push the signal cable into the hole of the signal cable inlet on the top of the rack and connect it to the terminal block in the rack, as shown in Figure 4-3. Step 4 Use the binding strap to fix the signal cable to the proper position in the device. InfraSuite - CoolDoor...
  • Page 37 (Figure 4-3: Upper Incoming Signal Cable) Connect the signal cable (lower incoming cable) Step 1 Use needle-nose pliers to remove the knockers at the bottom of the rack, and then take out the cable protection ring from the accessory bag. Put the protection ring on the perforated hole, as shown in Figure 4-4.
  • Page 38 Figure 4-5. Step 4 Use the binding strap to fix the signal cable to the proper position in the device. (Figure 4-5: Lower Incoming Signal Cable) InfraSuite - CoolDoor...
  • Page 39: Panel Diagram

    Panel Diagram Power panel (Figure 4-6: Power Control Panel Diagram) Item Description Item Description Main power fuse Fan 4 power fuse Backup power fuse Dual power over switch relay Terminal block Power supply unit 1&2 fuse Fan 1 power fuse Power supply unit 1 Fan 2 power fuse Power supply unit 2...
  • Page 40 Item Description Item Description SNMP card Control board This device is equipped with a Delta SNMP card, which can establish a connection with the workstation and Display & SNMP slot IO connect monitor and manage the system board through SNMP protocol.
  • Page 41 (Figure 4-9: Signal Interface Contact) X3 terminal block contacts 1–10 • Item Description Item Description Item Description Item Description Power input Power supply (AC-L) 3 power input Input dry Fan 1 status Fan 1 speed PWM 1 output contact feedback control Input dry Fan 2 status...
  • Page 42 GND supply GND signal GND Differential Light bar pressure BACnet power Fan 4 signal (blue) power sensor supply GND supply GND power supply Control valve 17A 24VDC input power input Solenoid valve 18A 24VDC input power input InfraSuite - CoolDoor...
  • Page 43 (Figure 4-10: External Signal Interface Contact) X3 terminal block contacts 19–26 • Suggest using cables with wire diameter of 22 AWG or larger and connecting the cables to user-supplied cord end terminals. The length of each terminal must be12 mm. Item Description Cable...
  • Page 44 CAN-Link contacts allow you to use one-in, one-out CAN-Link serial connection configuration for group control. 22 AWG 3C contact 25B (CAN-H), 26B (CAN-L), 16B (GND) InfraSuite - CoolDoor...
  • Page 45: Chapter 5 : Initial Start-Up

    Chapter 5 : Initial Start-up Inspection Prior to Activation WARNING:  Only qualified service staff may perform the installation steps hereunder. WARNING:  This equipment contains high voltage that can be fatal! Make sure that the power is disconnected before you perform the following. WARNING: ...
  • Page 46: Operating Temperature & Humidity

    If the indoor humidity is too high and the chilled water temperature is too low, condensation around the coil may generate too much condensate, which will lead to leakage on the indoor floor. Ensure that the chilled water temperature is always higher than the dew point temperature of the indoor environment. InfraSuite - CoolDoor...
  • Page 47 Out of operation range Water Inlet Temp 64.4 ° F Water Inlet Temp 59 ° F Water Inlet Temp 53.6 ° F Indoor ambient temperature (°F)
  • Page 48: Power Supply

    The following actions can only remove the air in the coil of the CoolDoor, and cannot ensure that the air in the closed chilled water system is completely removed. The air release valve should be used for automatic exhaust at the highest and most reasonable point of the closed circuit system.
  • Page 49 2. When making adjustments, the closed chilled water circuit should be in operation. Find the position of the exhaust valve on the CoolDoor, as shown in the figure below. Turn the cap to the right, and install the filling soft tube inlet with a switch on the position of the exhaust valve on the CoolDoor, as shown in the figure below.
  • Page 50: Water Volume Equilibrium

    CoolDoors is relatively long, it is easy to cause water imbalance. Unbalanced water volume can easily cause insufficient water volume at the last of the CoolDoor; or when controlled by a 2-way control valve, it can cause drastic changes in the water volume of other CoolDoors, which will make the overall waterway system unstable.
  • Page 51: Chapter 6 : Operation

    Chapter 6 : Operation Menu Tree Main Internal functions involve Screen important settings, which must be operated by Delta professional personnel. Main menu Alarm Power Status Setting Administrator ON/OFF System Setpoint Local Setting Controller Set Alarm Sensor Run Hours Alarm...
  • Page 52: Control Panel

    When the red light is on, it means there is a fault message. ▲▼ Page up or down, move the highlighted area or select a character code. Return to the previous screen or stop the current operation. Enter selected option or confirm settings. InfraSuite - CoolDoor...
  • Page 53: Status Page Operation

    On the Main Screen press Alarm to enter and view. Select Enable and Standby on this page. Selecting ON will make the CoolDoor System Mode start running; it will be automatically ON Standby controlled according to IT Rack heat load and the set temperature.
  • Page 54 Main menu → Status → Run Hours, System press key to enter. Fan 1 CoolDoor will record the running time of Fan 2 the system, and record the running time Fan 3 of the fan and the ball valve. If important...
  • Page 55 The No: XXX/XXX above indicates the order of events, <XXX> represents the event code, the time is in YY/MM/DD hh:mm:ss, and the event name is displayed to the side of NOTE: maximum number Event Log display items is 200. Main menu → Setting, press to enter.
  • Page 56 7. Display Unit: The user can choose units according to their region: BS British system/ MS metric system. 8. Total Alarm: Delta CoolDoor design dry contact output; you can use this status point for assistance, and notify the host computer function according to the severity of the CoolDoor system.
  • Page 57 11. LED Light Bar: You can turn on or turn off the Light Bar function below. 12. Fire. Cut-Off: When ON is selected, and the CoolDoor fire and smoke dry contact receives a status transition signal, the CoolDoor will execute the standby state, and the fan and ball valve will be completely closed.
  • Page 58 Condensation :☑ temperature sensor is an optional Fire Detection:☑ accessory). 4. Remote Sensor: Delta CoolDoor can detect the temperature and humidity of the channel environment, and you can choose whether to produce an alarm when the temperature and humidity sensors are abnormal (the remote temperature sensor is an optional accessory).
  • Page 59 6. Fire Detection: Select ☑ ; an alarm will be generated when the fire and smoke dry contact status transitions. Main menu → Setting → Set Alarm Ball Valve :☑ → Actuator Alarm, press key to Fan 1 :☑ enter. Fan 2 :☑...
  • Page 60 When the water inflow is lower than the configured value, an alarm will be generated. 10. Water Flow Rate Low: It can be turned on by ☑ ; an appropriate temperature value according to customer needs. When InfraSuite - CoolDoor...
  • Page 61 the water inflow is lower than the configured value, an alarm will be generated.
  • Page 62: Account Access Authorization & Log-In

    Turbo Boost provides leakage, ball valve, fan and condensation protection. Step 1 After installing the CoolDoor duct on the rack (see Chapter 3.4.2), use a Phillips screwdriver to remove the covers on both sides as shown in Figure 6-1. Please note that there is no need to remove the outermost covers of the first and last ducts (see Figure 6-2).
  • Page 63 Remove the covers on both sides (total: 10 pieces) (Figure 6-1: CoolDoor Duct Side Covers) The outermost covers of the first duct The outermost covers of the last duct (Figure 6-2: The Outmost Covers of the First and Last Ducts)
  • Page 64 CAN-Link (see Figure 4-10), you can use the CAN-Link to set up each CoolDoor. Step 4 Set up each CoolDoor ID. The IDs must be consecutive (for example 1, 2, 3 and so on) for the adjacent CoolDoors. Step 5 Turn on the Turbo boost.
  • Page 65: Chapter 7 : Fault Code & Descriptions

    Power the circuit breaker. powered on. Check if the power The fuse installed in the communication cable of the TP is CoolDoor’s fuse holder is Unable to start up normal. failed. Check if the single screen can be The power cable of the touch...
  • Page 66 Water leakage at the bottom of the Confirm whether the installation is unit damaged by collision. Coil damage and leakage. Confirm that the supply water pressure is correct. Leakage line sensor failure. Replace the leakage line sensor. InfraSuite - CoolDoor...
  • Page 67: Warning Codes

    Phenomenon Possible cause Troubleshooting Instructions Check if the connections to the Abnormal Touch The connections are wrong. console are correct; restart the Panel display or distribution board if necessary. absence of display Screen failure Replace with a new screen. Warning Codes Alert Event System Action...
  • Page 68 100% Fan CH1 1. Alarm display 1. Check the fan Abnormal 1. Fan terminal is wiring 2. One fan fails; loose the minimum 2. Remove foreign Fan CH2 speed is 70% objects and Abnormal InfraSuite - CoolDoor...
  • Page 69 Alert Event System Action Method of Alarm Name Level Possible Cause after Alarm Exclusion 3. More than two 2. The blade is confirm that the Fan CH3 fans fail; the stuck due to blades are not Abnormal minimum foreign matter damaged speed is 100% Fan CH4...
  • Page 70 2. The air setting Remote T High Alarm display setting for each is abnormal outlet is correct 3. The configured 3. Check the value of the configured value alarm is of the alarm incorrect InfraSuite - CoolDoor...
  • Page 71 Alert Event System Action Method of Alarm Name Level Possible Cause after Alarm Exclusion 1. Confirm whether 1. The air setting the temperature is abnormal setting for each 2. The configured outlet is correct Remote T Low Alarm display value of the 2.
  • Page 72 High condition of the too low chilled water 3. The configured circuit pump is value of the normal alarm is 3. Check the incorrect configured value of the alarm * : 1 means Warning; 2 means Severe InfraSuite - CoolDoor...
  • Page 73: Chapter 8 : Maintenance & Cleaning

    Component Maintenance 1. Coil and door maintenance The CoolDoor does not have a filter to filter the air. The system will first cool the air through the coil and then send it out through the fan. Therefore, the coil can easily become blocked by dust from the air in the IT room.
  • Page 74: Component Replacement

    Component Replacement Before performing power-off maintenance, the main door of the CoolDoor should be opened. The server can use its own fan to dissipate heat to avoid poor heat dissipation for the server. When troubleshooting or replacing components, ensure that the CoolDoor power is correctly turned off.
  • Page 75 Figure 2, and take out the fan. Finally, remove the four screws around the fan motor at position 3 below with a screwdriver to separate the fixed plate from the fan. Install the new fan back onto the CoolDoor in the reverse order to complete the fan replacement.
  • Page 76: Quarterly Maintenance

    Check whether the cut off valve connection line is off (optional) Finished Check whether the flow meter connection line is off (optional) Check whether the dew point temperature sensor cable is off Finished (optional) General Check Whether the sampled water quality meets the specifications Finished InfraSuite - CoolDoor...
  • Page 77 ((!)) The following tests will be carried out with a power supply and should be tested by professionally trained personnel. Open the front electric panel door and confirm the following: When there is no alarm, input the power of Feed A, and whether Finished the LED light bar is blue When there is no alarm, input the power of Feed B, and whether...
  • Page 78: Chapter 9 : Modbus Table

    0x118 Chilled Water Flow Rate 2 Bytes 0.1LPM Ball valve opening 0x119 2 Bytes 0.1% 0.0-100.0% feedback Fan 1 failure Fan 2 failure Fan 3 failure 0x121 DI Status Flag 1 2 Bytes Null Fan 4 failure InfraSuite - CoolDoor...
  • Page 79 Address Description Length Unit Note b10: b11: b12: b13: b14: b15: 0x14B Return air T 1 2 Bytes 0.1°C 0x14C Return air T 2 2 Bytes 0.1°C 0x14D Return air T 3 2 Bytes 0.1°C 0x14E Supply air T 1 2 Bytes 0.1°C 0x14F...
  • Page 80: Appendix 1 : Specifications

    Abnormal Alarm (Red) SA control via PI turning SA control via PI turning (default) (default) Ball Valve Control Pressure independent Pressure independent control (optional) control (optional) Water Leakage Standard, 4m in length Standard, 4m in length Detector InfraSuite - CoolDoor...
  • Page 81 Model No. Unit RWC030D0AK00B8 RWC050D0AK00B8 1. Fan failure 1. Fan failure Increase the fan speed Increase the fan speed of neighboring of neighboring machines. machines. 2. Ball valve failure 2. Ball valve failure Reduce the air outlet Reduce the air outlet temperature setting of temperature setting of Turbo Boost...
  • Page 82: Appendix 2 : Warranty

    The User Manual must be carefully followed. Seller makes no representation or warranty as to the suitability or fitness of this product for any specific application. No. : 501329580000 Version : V 0.0 Release Date : 2021_10_14 InfraSuite - CoolDoor...
  • Page 83 - Regional Office The United States Australia Delta Electronics (Americas) Ltd. Delta Energy Systems Australia Pty Ltd. 46101 Fremont Blvd. Fremont, CA 94538 Unit 20-21, 45 Normanby Road, Notting Hill VIC 3168, Australia T +1 510 344 2157 T +61 3 9543 3720 E ups.na@deltaww.com...
  • Page 84 5013295800...

This manual is also suitable for:

Rwc050d0ak00b8

Table of Contents