Download Print this page

Compatibility Requirements; Installation Steps - Honeywell Notifier NZM-100-6 Installation And Maintenance Instructions Manual

Six zone interface module

Advertisement

unused modules to release the addresses to be used elsewhere. Each mod-
ule also has panel controlled bicolor LED indicators. The panel can cause the
LEDs to blink, latch on, or latch off.
Included:
(5) 1 x 4 Terminal Blocks
(2) 1.25" Stand offs
(4) Machine Screws
(2) Nuts
(6) 3.9k Ohm End of Line Resistors
Shipped on Board:
(2) Shunts in Class A/B position
(Shipped in Class B position, remove shunts for Class A)

COMPATIBILITY REQUIREMENTS

To ensure proper operation, this module shall be connected to a compatible
system control panel (list available from ). Contact System Sensor for a current
list of compatible detectors.
COMPONENTS
Following are descriptions of the NZM-100-6 mounting frameworks. There are
two mounting options for NZM-100-6 modules:
• Up to six NZM-100-6 modules can be installed on a CH-6 in a BB-25
cabinet
• One or two NZM-100-6 modules can be installed in a BB-XP cabinet
Chassis
The CH-6 chassis is used to mount NZM-100-6 modules in a BB-25 cabinet.
It accommodates up to six NZM-100-6 modules in a single cabinet row three
modules wide and two modules deep.
FIGURE 1. CH-6 CHASSIS
The BB-XP cabinet has a built-in chassis that will accommodate one or two
NZM-100-6 modules.
FIGURE 2. BB-XP CABINET
The front NZM-100-6 module positions of each chassis are offset below the
rear NZM-100-6 module positions so that all of the status indicators are visible.
(3) Shunts
(1) Long Power Supply Jumper
C0202-00
C0206-00
C0235-00
Cabinets
A BB-25, CAB-3, or CAB-4 Series cabinet will house the CH-6 chassis with up
to six NZM-100-6 modules installed on it. Refer to cabinet installation docu-
ments for dimensions.
The BB-XP cabinet houses one or two NZM-100-6 modules on the internal
chassis that is part of the cabinet. Refer to cabinet installation documents for
dimensions.

INSTALLATION STEPS

1.
Cabinet Mounting
In a clean, dry area, mount the backbox using the four holes provided in
the back surface of the cabinet (Figure 3).
2.
Chassis Installation
The CH-6 chassis is mounted in the BB-25, CAB-3, or CAB-4 Series cabi-
net. It is shipped with two self-threading screws, which are used to fas-
ten the chassis to the back wall of the cabinet (Figure 4).
FIGURE 3. TYPICAL MOUNTING HOLE LOCATIONS
FIGURE 4. MOUNTING THE CH-6 CHASSIS
The BB-XP cabinet comes with the chassis already installed, so no mounting
is necessary.
3. Module Installation
There are two methods for installing a module in the rear position of a
chassis. Method one is for installation of a rear module only, when no
module will be installed in front of it. Refer to Figure 5 for instructions.
Method two is for installation of a rear module when another module
will be installed in the chassis position in front of it. Refer to Figures 6a
and 6b for method two. All necessary screws and standoffs are supplied
with the modules.
FIGURE 5. INSTALLATION OF REAR MODULE ONLY, METHOD ONE
2
1
Step 1:
Insert the bottom of the NZM-100-6 module down into a rear slot
on the chassis.
2
BACKBOX
MOUNTING
HOLES
C0235-00
MOUNT WITH
SELF-THREADING SCREWS
TO BACK OF CABINET
C0236-00
3
C0237-00
I56-2990-004