Electrical Characteristics - Fujitsu ASUH18LPAS Design & Technical Manual

Wall mounted type
Hide thumbs Also See for ASUH18LPAS:
Table of Contents

Advertisement

10. Electrical characteristics

Model name
Voltage
Power
supply
Frequency
MCA *1
Starting current
MAX. CKT. BKR *3
Power cable
Wiring
spec. *2
Connection
cable *4
*1: Minimum Circuit Ampacity (Calculation based on UL60335-2-40)
*2: Selected sample based on Japan Electrotechnical Standards and Codes Committee E0005. As
the regulations of wire size and circuit breaker differ in each country or region, select appropriate de-
vices complied to the regional standard.
*3: Maximum Circuit Breaker
*4: Limit voltage drop to less than 2%. If voltage drop is 2% or more, increase cable conductor size.
V
Hz
A
A
A
AWG
Size
AWG
Limited
wiring
ft (m)
length
AOUH18LPAS1
208/230~
60
14.7
6.7
15
14
14
69 (21)
- 76 -
AOUH24LPAS1
17.2
11.4
20
10. Electrical characteristics