Capacity Compensation Rate For Pipe Length And Height Difference; Models: Aouh18Lpas1 And Aouh24Lpas1 - Fujitsu ASUH18LPAS Design & Technical Manual

Wall mounted type
Hide thumbs Also See for ASUH18LPAS:
Table of Contents

Advertisement

6. Capacity compensation rate for pipe length and height
difference
Indoor unit is higher than outdoor unit
Indoor unit
Connection pipe

6-1. Models: AOUH18LPAS1 and AOUH24LPAS1

NOTE: Values mentioned in the table are calculated based on the maximum capacity.
COOLING
Indoor unit is higher than outdoor
unit *1
Indoor unit is lower than outdoor
unit *2
HEATING
Indoor unit is higher than outdoor
unit *1
Indoor unit is lower than outdoor
unit *2
6-1. Models: AOUH18LPAS1 and AOUH24LPAS1
Height difference H
1
*
H
Outdoor unit
m
ft
15
49
10
33
7.5
25
5
16
0
0
-5
-16
-7.5
-25
-10
-33
-15
-49
m
ft
15
49
10
33
7.5
25
5
16
0
0
-5
-16
-7.5
-25
-10
-33
-15
-49
- 71 -
Indoor unit is lower than outdoor unit
Outdoor unit
H
Indoor unit
Connection pipe
Pipe length
5
7.5
10
16
25
33
-
-
-
-
-
0.979
-
0.988
0.983
0.994
0.992
0.987
1.002
1.000
0.995
1.002
1.000
0.995
-
1.000
0.995
-
-
0.995
-
-
-
Pipe length
5
7.5
10
16
25
33
-
-
-
-
-
1.012
-
1.000
1.012
0.969
1.000
1.012
0.969
1.000
1.012
0.964
0.995
1.007
-
0.993
1.004
-
-
1.002
-
-
-

6. Capacity compensation rate for pipe length and height difference

2
*
15
20
49
66
0.951
0.950
0.967
0.966
0.971
0.970
0.975
0.974
0.983
0.982
0.983
0.982
0.983
0.982
0.983
0.982
0.983
0.982
15
20
49
66
0.994
0.979
0.994
0.979
0.994
0.979
0.994
0.979
0.994
0.979
0.989
0.974
0.986
0.972
0.984
0.969
0.974
0.959