6.2.2

Terminal box

Hazardous voltage
Electric motors have high voltages. When incorrectly handled, this can result in death or severe
injury.
Switch off the machine so that it is in a no-voltage condition before you open the terminal box.
NOTICE
Damage to the terminal box
If you incorrectly carry out work on or in the terminal box, this can result in material damage.
You must observe the following to avoid damaging the terminal box:
• Ensure that the components inside the terminal box are not damaged.
• It must be ensured that there are no foreign bodies, dirt or moisture in the terminal box.
• Close the terminal box using the original seal so that it is dust tight and water tight.
• Use O-rings or suitable flat gaskets to seal entries in the terminal box (DIN 42925) and other
• Please observe the tightening torques for cable entries and other screws.
• Do not apply manual force to the terminal board. The terminal board mountings are
6.2.2.1

Circuit diagram inside the terminal box cover

Data on the connection and connecting the machine winding can be found in the circuit
diagram in the cover of the terminal box.
6.2.2.2

Direction of rotation

The standard motors are suitable for clockwise and counter-clockwise rotation.
For defined directions of rotation (direction of rotation arrow), appropriately connect the line
power cables.
• If you connect the line cables with phase sequence L1, L2, L3 at U, V, W or according to NEMA
at T1  T2  T3 , then the machine rotates in the clockwise direction.
• If you interchange 2 connections, e.g. L1, L2, L3 at V, U, W or according to NEMA at T2 T1 T3,
then the machine rotates counterclockwise.
 
Line feeder cables
1LE5, 1PC4 shaft heights 280 ... 355
Operating Instructions, 11/2022, A5E41454666A
DANGER
open entries.
designed for the cable sizes specified in the documentation.
Direction of ro‐
tation
-
According to IEC
L1  L2  L3
Electrical connection
6.2 Connecting the machine
According to NEMA
L1  L2  L3
67