Forced Cooling Operation; Economy Operation; Powerful Operation - Fujitsu General ASHG07KPCE Service Manual

Wall mounted type
Table of Contents

Advertisement

7-3. Forced cooling operation

The outdoor unit may not operate depending on the room temperature.
When FORCED COOLING OPERATION button is pressed more than 10 seconds, forced cooling
operation starts as shown in the table below.
Operation mode
Fan mode
Timer mode
Setting temperature
Vertical airflow direction louver setting
Horizontal airflow direction louver setting
SWING
ECONOMY
Human sensor
• During the forced cooling operation, it operates regardless of room temperature sensor.
• The operation indicator lamp and the timer indicator lamp blink simultaneously during the forced
cooling operation.
They blink for 1 second ON and 1 second OFF on both the operation indicator lamp and the timer
indicator lamp (same as test operation).
By performing one of the following action, test operation will be canceled:
• Pressing the remote controller START/STOP button
• Pressing FORCED COOLING OPERATION button for 3 seconds
• 60 minutes passed after starting forced cooling operation
NOTE: When HEAT operation is selected on the remote controller during forced cooling operation,
heating test run will begin in about 3 minutes.

7-4. ECONOMY operation

The ECONOMY operation starts by pressing ECONOMY button on the remote controller.
The ECONOMY operation is almost the same operation as below settings.
Mode
Target temperature

7-5. POWERFUL operation

The POWERFUL operation starts by pressing POWERFUL button on the remote controller.
The indoor unit and outdoor unit operate at maximum power as shown in the table below.
Rotation number of compressor
Fan mode
Vertical airflow direction
louver setting
Release condition:
• Cooling/Dry
Room temperature ≤ Setting temperature -0.5°C or Operation time has passed 20 minutes.
• Heating
Room temperature ≥ Setting temperature +0.5°C or Operation time has passed 20 minutes.
7-3. Forced cooling operation
Cooling/Dry
Setting temperature +1°C
Cooling
Dry
Heating
- (04-24) -
Cooling
HIGH
Continuous (no timer setting available)
24°C
Standard
According to memory position
Off
Off
Off
Heating
Setting temperature -1°C
Maximum
POWERFUL
3
6
7. Various control