1. Specifications Wall mounted Type Inverter heat pump Model name ASHG18KLCA ASHG24KLCA Power supply 230 V ~ 50 Hz Available voltage range 198—264 V 5.20 7.10 Rated Btu/h 17,700 24,200 Cooling 0.9—5.5 0.9—7.7 Min.—Max. Btu/h 3,000—18,700 3,000—26,200 Capacity 6.30 8.00 Rated Btu/h 21,400...
Page 7
Model name ASHG18KLCA ASHG24KLCA Cooling Energy efficiency class Heating (Average) Cooling 5.2 (35 °C) 7.1 (35 °C) Pdesign Heating (Average) 4.8 (-10 °C) 7.1 (-10 °C) SEER Cooling 7.20 7.10 kWh/kWh SCOP Heating (Average) 4.30 4.00 Annual energy consumption kWh/a QHE (Average) 1,563 2,485...
2. Dimensions 2-1. Models: ASHG18KLCA and ASHG24KLCA Unit: mm Outline of indoor unit for pipe inlet Ø65 for pipe inlet Ø65 - 4 - 2-1. Models: ASHG18KLCA and ASHG24KLCA 2. Dimensions...
Page 9
¢ Installation space requirement Provide sufficient installation space for product safety. Unit: mm 48 or more 52 or more Wall hook bracket Outline of the indoor unit 70 or more 85 or more 1,500 or more The flare connection part should be installed outdoors.
4. Capacity table Capacity tables show each of following values calculated based on the outdoor temperature and the indoor temperature, under given Airflow Rate (AFR): For cooling capacity: Total Capacity (TC), Sensible Heat Capacity (SHC), and Input Power (IP) For heating capacity: Total Capacity (TC) and Input Power (IP) 4-1.
5. Fan performance 5-1. Air velocity distributions ¢ Model: ASHG18KLCA Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center Unit: m/s Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Left &...
Page 14
¢ Model: ASHG24KLCA Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center Unit: m/s Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Left & Right Unit: m/s Side view Vertical airflow direction louver: Up...
6-2. Sound level check point Microphone Microphone NOTE: Detailed shape of the actual indoor unit might be slightly different from the one illustrated above. - 14 - 6-2. Sound level check point 6. Operation noise (sound pressure)
7. Safety devices Model Type of protection Protection form ASHG18KLCA ASHG24KLCA Circuit protection Current fuse (PCB*) 250 V, 3.15 A 150±15 °C Activate Fan motor stop Fan motor protection Thermistor protection 120±15 °C Reset Fan motor restart *PCB: Printed Circuit Board - 15 - 7.
8. Remote controller 8-1. Wireless remote controller ¢ Overview a FAN button b SET button c SWING button d START/STOP button e RESET button f TIMER CANCEL button g ON TIMER button h OFF TIMER button i SLEEP TIMER button j TEST RUN button •...
Page 21
¢ Specifications Controller Unit: mm Top view Front view Side view Rear view Size (H × W × D) 139 × 56 × 18 Weight 70 (without batteries) Holder Unit: mm 60.4 30.2 Ø 3.5 (hole) 3.5 x 6.5 (hole) 26.2 Front view...
9. Function settings To adjust the functions of this product according to the installation environment, various types of function settings are available. NOTE: Incorrect settings can cause a product malfunction. 9-1. Function settings by using remote controller Some function settings can be changed on the remote controller. After confirming the setting proce- dure and the content of each function setting, select appropriate functions for your installation envi- ronment.
Page 23
STEP 2: Selecting the function number and setting value 1. Press the SET TEMP. ( ) buttons to select the function num- Function number ber. To switch between the left and right digits, press the MODE button. 2. Press the FAN button to proceed the setting value. To return the function number selection, press the FAN button again.
Page 24
¢ Contents of function setting Each function setting listed in this section is adjustable in accordance with the installation environ- ment. NOTE: Setting will not be changed if invalid numbers or setting values are selected. Function setting list Function no. Functions Filter sign 30/31...
Page 25
3) Auto restart Enables or disables automatic restart after a power interruption. Function number Setting value Setting description Factory setting Enable ♦ Disable NOTE: Auto restart is an emergency function such as for power outage etc. Do not attempt to use this function in normal operation.
9-2. Custom code setting for wireless remote controller To interconnect the air conditioner and the wireless remote controller, assignment of the custom code for the wireless remote controller is required. NOTE: Air conditioner cannot receive a custom code if the air conditioner has not been set for the custom code.
1. Specifications Type Inverter heat pump Model name AOHG18KLTA AOHG24KLTA Power supply 230 V ~ 50 Hz Available voltage range 198—264 V Starting current 10.9 Cooling 1,830 2,885 Airflow rate Heating 2,265 3,030 Type × Q'ty Propeller fan × 1 Motor output Cooling Sound pressure level *1...
2. Dimensions 2-1. Model: AOHG18KLTA Unit: mm 4-M10 hole Pitch of bolts for installation Top view Side view Front view Side view Airflow Drain port Ø42 Bottom view Side view (Valve part) - 27 - 2-1. Model: AOHG18KLTA 2. Dimensions...
2-2. Model: AOHG24KLTA Unit: mm 4-M10 hole Pitch of bolts for installation Top view Side view Front view Side view Airflow Drain port Ø42 Bottom view Side view (Valve part) - 28 - 2-2. Model: AOHG24KLTA 2. Dimensions...
3. Installation space 3-1. Models: AOHG18KLTA and AOHG24KLTA ¢ Space requirement Provide sufficient installation space for product safety. CAUTION Keep the space shown in the installation examples. If the installation is not performed accordingly, it could cause a short circuit and result in a lack of operating performance.
Page 34
Multiple outdoor unit installation • Provide at least 250 mm of space between the outdoor units if multiple units are installed. • When routing the piping from the side of an outdoor unit, provide space for piping. • No more than 3 units must be installed side by side. When 3 units or more are arranged in a line, provide the space as shown in the following ex- ample “When an obstruction in the upper space:”.
Page 35
Outdoor units installation in multi-row Unit: mm Single parallel unit arrangement Multiple parallel unit arrangement 100 or more 200 or more 1,000 or more 2,000 or more 200 or more 400 or more 500 or more 1,000 or more 200 or more 250 or more 1,000 or more...
6. Capacity compensation rate for pipe length and height difference Height difference H Indoor unit is higher than outdoor unit Indoor unit is lower than outdoor unit Outdoor unit Indoor unit Outdoor unit Indoor unit Connection pipe Connection pipe 6-1. Model: AOHG18KLTA NOTE: Values mentioned in the table are calculated based on the maximum capacity.
6-2. Model: AOHG24KLTA NOTE: Values mentioned in the table are calculated based on the maximum capacity. Pipe length (m) COOLING — — — — — 0.893 0.877 — — — — 0.917 0.900 0.885 Indoor unit is higher — — 0.966 0.947 0.932...
9-2. Sound level check point Rear Microphone Microphone Airflow Side view Rear view NOTE: Detailed shape of the actual outdoor unit might be slightly different from the one illustrated above. - 40 - 9-2. Sound level check point 9. Operation noise (sound pressure)
10. Electrical characteristics Model name AOHG18KLTA AOHG24KLTA Voltage 230 ~ Power supply Frequency Max operating current *1 13.5 17.5 Starting current 10.9 Circuit breaker current Wiring Power cable spec. Cross-sectional area Connection cable *3 Limited wiring length *1: Maximum operating current is the total current of the indoor unit and the outdoor unit. *2: Selected sample based on Japan Electrotechnical Standards and Codes Committee E0005.
11. Safety devices Model Type of protection Protection form AOHG18KLTA AOHG24KLTA 250 V, 20 A 250 V, 25 A Circuit protection Current fuse (Main PCB) 250 V, 5 A — 250 V, 3.15 A 100±15 °C 125±10 °C Activate Fan motor stop Fan motor stop Fan motor Terminal protection...
12. Accessories 12-1. Models: AOHG18KLTA and AOHG24KLTA Part name Exterior Q’ty Part name Exterior Q’ty Installation manual Drain pipe - 43 - 12-1. Models: AOHG18KLTA and AOHG24KLTA 12. Accessories...