5-2. Outdoor unit

¢ Heatsink thermistor
Temperature (°C)
-30.0
-25.0
-20.0
-15.0
-10.0
-5.0
0.0
5.0
10.0
15.0
20.0
25.0
30.0
35.0
40.0
45.0
50.0
55.0
60.0
65.0
70.0
75.0
80.0
85.0
90.0
95.0
100.0
5-2. Outdoor unit
Resistance (kΩ)
94.26
67.95
49.62
36.68
27.42
20.73
15.83
12.21
9.50
7.46
5.90
4.71
3.78
3.06
2.50
2.05
1.69
1.40
1.17
0.98
0.83
0.70
0.60
0.51
0.44
0.38
0.33
- (03-68) -
Voltage (V)
0.08
0.11
0.15
0.20
0.26
0.34
0.43
0.55
0.68
0.84
1.01
1.21
1.42
1.64
1.88
2.11
2.35
2.58
2.81
3.02
3.22
3.41
3.58
3.73
3.87
3.99
4.10