Switch SW1 - Ground Fault Detection
Note: The HPF-PS6 uses the same PCB
layout, however some terminals will be
depopulated, leaving the HPF-PS6 with
five output circuits and two inputs circuits.
TB4 AC Power
Supervised,
Non-power-limited
AC2 (Neutral)
Earth
AC (Hot)
SW1 Ground Fault
Detection
(slide left to disable)
(slide right to enable)
TB15 Supervised
+ Battery
- Battery
24 VDC
Non-power-limited
HPF-PS Series Instruction Manual — P/N LS10227-003HP-E:C 2/2/2022
Form-C
Fail-Safe Relays
Non-supervised
(shown energized)
AC1
AC2
TB15
Global
Output 7
Options
S1
Programming DIP Switch
for global options
Figure 1.1 HPF-PS10 Board Layout
Power-limited (Class 2), Supervised, Special
Application or Regulated Outputs
Output 6
Output 5
Output 4
Output 3
NAC/Out 7 -
NAC/Out 7 +
NAC/Out 6 -
NAC/Out 6 +
NAC/Out 5 -
NAC/Out 5 +
NAC/Out 4 -
NAC/Out 4 +
NAC/Out 3 -
NAC/Out 3 +
NAC/Out 2 -
NAC/Out 2 +
NAC/Out 1 -
NAC/Out 1 +
Output Status LEDs
Trouble (yellow)
Power (red)
J8
ZNAC-PS Connector
LEDs
Power (green)
Batt/Chgr Fault (yellow)
Ground Fault (yellow)
Output 2
Output 1
S2-S8
Programming DIP Switches
Activate output DIP switch changes by setting S1
positions 9 and 10 appropriately. Refer to page
page 27 for DIP Switch programming settings.
Each output circuit has its own dedicated
programming DIP switch
System Overview
TB5, TB6, TB7
Command Inputs
Input #1
A+
B-
B+
A-
Input #2
A+
B-
B+
A-
Input #3
A+
B-
B+
A-
11

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hpf-ps6eHpf-ps6bHpf-ps10Hpf-ps10eHpf-ps10b

Table of Contents