Tracking Transfer Setting - Mitsubishi Electric MELSEC iQ-R Series User Manual

Process cpu module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Tracking transfer setting

The following describes the CPU parameters related to tracking transfer.
[CPU Parameter]  [Redundant System Settings]  [Tracking Setting]
Window
Displayed items
Item
Description
Signal Flow Memory
Set whether to transfer the signal flow memory or not. ( Page 396
Tracking Setting
Tracking transfer setting for the signal flow memory)
Tracking Device/Label
Set "Transfer collectively" or "Detailed setting" for devices or labels to be
Setting
transferred.
• When "Transfer collectively" is set, global devices, local devices, global
labels, module labels (extension base unit), and local labels are assigned
to the tracking block No.1 and automatically transferred. ( Page 397
Batch transfer)
• When "Detailed setting" is set, detailed settings can be configured in
"Tracking Block No.1 Auto Transfer Setting" and "Device/Label Detailed
Setting".
Tracking Block No.1 Auto
Set whether to automatically transfer the tracking block No.1 or not. (
Transfer Setting
Page 393 Tracking block and tracking trigger)
Device/Label Detailed
Set devices and labels to be transferred. ( Page 398 Detailed setting)
Setting
Set "Detailed setting" of "Tracking Device/Label Setting" for the following purposes.
• To shorten a tracking transfer time
• To add tracking data, such as the file register (ZR)
• To transfer each data set individually
When the "Process Control Extension Setting" is enabled
Settings and operations are as follows:
• When a program file is converted, "Tracking Device/Label Setting" is automatically set to "Detailed setting".
• In the tracking block No.64, the range of the file register specified in the system resource of the process control extension
setting is registered. Because the other devices are not automatically registered, specify the other tracking block numbers
for those devices. The devices and their ranges set in "Device/Label Memory Area Setting" can be imported at a time by
clicking the [Device Setting Reflection] button in the "Global Device Setting" window. ( Page 399 Global device setting)
• To transfer the tracking block No.64, the bit 15 of SD1670 automatically turns on at every scan when the system is
operating in backup mode. Do not turn off the bit 15 of SD1670.
Setting range
Default
• Do Not Transfer
Transfer
• Transfer
• Transfer collectively
Transfer collectively
• Detailed setting
• Do Not Transfer
Transfer Automatically
Automatically
• Transfer
Automatically
26 REDUNDANT FUNCTION
26.3 Tracking Transfer
26
395