Auto Logging - Mitsubishi Electric MELSEC iQ-R Series User Manual

Process cpu module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

20.11

Auto Logging

When inserting an SD memory card, which holds data logging setting, into the CPU module, the data logging automatically
starts based on the data logging setting information on the SD memory card.
How to use auto logging
This section describes how to use auto logging.
1.
Prepare an SD memory card that contains data logging settings as well as common settings (auto logging common
settings) in which auto logging is enabled.
2.
Insert the SD memory card prepared in step 1 into the CPU module while it is running.
3.
When the SD memory card is inserted, data logging starts automatically. (CARD READY LED and CARD ACCESS LED
turn on.)
4.
Check that auto logging is completed on the engineering tool or using the LED
5.
Remove the SD memory card.
*1 When "Data Logging Function" is set in the LED indicator setting, the FUNCTION LED flashes every 200ms. If the executed function
has higher priority of the FUNCTION LED than the function set in the LED indicator setting, the data logging function status is not
displayed. ( Page 206 LED display setting)
• Even when the data logging stop operation is performed after auto logging starts, auto logging does not end
until when the SD memory card is removed.
• To use auto logging, the auto logging common setting file and data logging setting file for operation are
required in the SD memory card.
• Write the auto logging common setting file to the SD memory card only when using auto logging. When auto
logging is not used, delete the auto logging common setting file. ( CPU Module Logging Configuration
Tool Version 1 Operating Manual (MELSEC iQ-R Series))
20 DATA LOGGING FUNCTION
290
20.11 Auto Logging
*1
on the CPU module.

Advertisement