Samsung AJ040TXJ2KG/EU Technical Data Book page 312

Free joint multi for europe r32, 50hz, hp
Table of Contents

Advertisement

13. Installation
Outdoor-to-indoor power and communication cables
specifications
Indoor power supply
Power supply
1Φ, 220-240V, 50 Hz
Communication cable
0.75 to 1.5 mm², 2 wires
• Power supply cords of parts of appliances for outdoor
use shall not be lighter than polychloroprene
sheathed flexible cord. (Code designation IEC:60245
IEC 57 / CENELEC: H05RN-F or IEC:60245 IEC 66 /
CENELEC: H07RN-F)
• When installing the indoor unit in a computer room
or net work room, server room or in the presence
of risk of disturbance to the communication cable,
use the double shielded (tape aluminium / polyester
braid + copper ) cable of FROHH2R type.
※ In case you want more information about the controllers and accessories, please refer to the Controller and Accessory TDB
on pvi.Samsung.com site or Global Partner Portal site.
312
Max/Min (V)
Indoor power cable
1.5 mm² ↑ , 3 wires
±10%
Connecting the refrigerant pipe
◆ AJ040/050TXJ2KG
1 Piping outside diameter
Indoor unit
Out unit
AR07/09/12********,
AJ040TXJ2KG
AJ026/035TN*D*G
AR07/09/12********,
AJ016/020/026
/035TN*D*G
AJ050TXJ2KG
AR18********,
AJ052TNJDKG
NOTE
• This product requires no additional refrigerant
charge up to the maximum allowable pipe length.
Maximum allowable refrigerant charge amount
AJ040TXJ2KG/EU
AJ050TXJ2KG/EU
• AJ040TXJ2KG Outdoor unit cannot be connected to
the following indoor unit combination.
- AJ0**TNNDKG/AJ0**TNLDEG
2 Piping outside diameter
1 Room
max
length
Dimension
20m
Composition
A,B
Outside diameter
Power supply
Ø, V, Hz
Liquid
1,220-240, 50
1/4"
1,220-240, 50
1/4"
(h) (H)
A
B
Main power switch
980 g
1180 g
Make at least one round:
It will reduce noise and vibration
Max height
2 Room
between
Max height
total max
indoor unit
between
length
& outdoor
indoor units
unit
30m
15m
A+B
(H)
Gas
3/8"
3/8"
1/2"
7.5m
(h)

Hide quick links: