Project engineering

4

Compatibility

4 Project engineering
4.1 Compatibility

4.2 Ranges of application

4.3 Installation site

4.4 Environmental influences

22 | 32
Building Technologies
Fire Safety
Compatible with all fire detection systems with collective/SynoLINE600 signal
processing. Refer to 'List of compatibility' (doc. no. 008331) for details.
The manual call points are intended for use in places where a fire can be detected
by people who can manually trigger an alarm.
The manual call points must be mounted in easily accessible places at a height of
1.3...1.6 m.
Observe the country-specific regulations for the exact mounting height!
If the devices are used in industrial applications, consultation with the project
manager is required, since plastics do not withstand certain environmental
conditions.
The following factors must be taken into consideration:
Chemicals
Temperature
Moisture
A6V10201150_d_en_--
2018-12-19