Actuator Operation - Emerson BETTIS G01 Series Disassembly And Reassembly

Hydraulic actuators spring-return actuators with m11 hydraulic override
Table of Contents

Advertisement

Service Instructions
127072E Rev. C
1�11�2 Check connections:
1�11�3 When actuator is first put into service, it should be cycled with regulated
1�11�4 The actuator speed of operation is determined by a number of factors including:
1�11�5 Due to the interaction of these variables, it is difficult to specify a "normal"
1�11�6 Slower operating times may be obtained by using flow control valves to meter the
1�12

Actuator Operation

1�12�1 Controlled Operation: Controlled operation is accomplished by pressurizing and/or
1�12�2 Manual Operation: All pressure must be vented or equalized on both sides of the
Introduction
4.
Indicated position confirms valve position
5.
All switching valves in normal operating position as per schematic/
instructions
1.
Hydraulic components connected as per schematic enclosed or in service
manual supplied
2.
Hydraulic supply connected to identified ports
3.
Electrical connections terminals are secure
4.
Wiring as per enclosed diagram or service manual supplied
pneumatic pressure. This is necessary because the seals have been stationary,
causing them to take a "set". Therefore, the actuator should be operated through
several cycles, exercising the seals, resulting in a service-ready condition.
1.
Power supply line length
2.
Power supply line size
3.
Power supply line pressure
4.
Control valve and fitting orifice size
5.
Torque requirements of the valve
6.
Size of the actuator
7.
Setting of speed controls
operating time. Faster operating times may be obtained by using one or more of
the following:
1.
Larger supply lines
2.
Larger control valve
3.
Higher supply pressure*
4.
Quick exhaust valves
*Not to exceed maximum operating pressure of actuator or control components
exhaust. Excessive exhaust flow metering may cause erratic operation.
depressurizing the appropriate cylinder inlet(s) of a double-acting or spring-return
unit by means of an appropriate control valve.
Do not exceed pressures indicated on actuator nameplate�
pneumatic piston prior to manual operation.
Section 1: Introduction
October 2015
5

Advertisement

Table of Contents
loading

Table of Contents