LG MULTI V ARN Series Engineering Manual page 18

Floor standing, ceiling suspended, and convertible surface mounted indoor unit
Hide thumbs Also See for MULTI V ARN Series:
Table of Contents

Advertisement

FLOOR STANDING
External Static Pressure and Air Flow Tables
CEU, CFU Uncased Units
Table 8: CEU Uncased Unit External Static Pressure and Air Flow Table.
Set Value
0
65
197
70
219
75
235
80
257
85
280
90
294
95
320
100
335
105
358
110
377
115
396
120
418
130
459
Table 9: CFU Uncased Unit External Static Pressure and Air Flow Table.
Set Value
0
65
330
70
373
75
408
80
440
85
481
90
508
95
534
100
582
105
611
110
644
115
681
120
709
130
787
1. All static pressure air flow rates are listed in CFM.
2. The tables above show the correlation between air flow rates and external static pressure.
3. The tables above show the available external static pressure range.
If the external static pressure of the installed indoor unit is less than the lowest value (as mentioned in the table), the indoor unit components
can fail.
18 | FLOOR STANDING
Static Pressure (in. wg)
0.04
0.08
115
25
138
26
183
52
209
99
236
155
256
181
267
208
281
245
315
268
337
298
359
323
378
349
420
397
Static Pressure (in. wg)
0.04
0.08
227
-
274
-
312
83
377
236
411
261
448
376
481
405
525
458
565
515
595
543
631
584
670
635
743
709
Due to our policy of continuous product innovation, some specifications may change without notification.
©
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
0.12
0.16
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
0.12
0.16
-
-
-
-
-
-
-
-
-
-
129
-
278
89
380
241
412
250
468
382
538
439
574
499
663
602
0.20
0.24
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
0.20
0.24
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
108
-
243
-
376
92
531
423