Ventilation And Cooling - Sullair ShopTek ST4 User Manual

4 - 15 kw (5 – 20 hp) three-phase 60 hz
Table of Contents

Advertisement

4: Installation

4.2 Ventilation and cooling

Table 4-1: Ventilation requirements
Model
ST4
ST5
ST7
ST11
ST15
• ShopTek compressors require a three foot (one
meter) clearance around their perimeter.
• The location should be free from standing
water.
• Clean air should be supplied to the compres-
sor, free from exhaust and paint fumes, dust,
metal particles, or caustic chemical vapors.
• Hot exhaust air should be vented out of the
area to prevent its recirculation back into the
compressor's cooling system.
• Ducting or some other means must be used to
ensure that hot exhaust air is vented away from
the compressor if the compressor's housing
has minimal overhead clearance.
Remove the red shipping straps/shipping studs
before operating the drive assembly. See Figure
4-1 and Figure 4-2.
34
ShopTek™ ST4, ST5, ST7, ST11, ST15 Three-phase 60 Hz User Manual
Ventilation air required
3
cfm
m
/hr
612
1040
612
1040
612
1040
1471
2500
1471
2500
NOTE
Subject to EAR, ECCN EAR99 and related export control restrictions.
Housing the compressor in an inadequately ven-
tilated enclosure will cause higher compressor
operating temperatures.
Figure 4-1: Shipping strap—ST4, ST5, ST7
88292018-236 R00
NOTE
1. Shipping strap