Table A — Physical Data (Cooling), 15 and 20 Tons — Round Tube/plate Fin (RTPF) Coil Design
REFRIGERATION SYSTEM
EVAP. COIL
EVAP. FAN AND MOTOR — VERTICAL
STANDARD
STATIC
MEDIUM STATIC
HIGH STATIC
MEDIUM STATIC
- HIGH EFF.
HIGH STATIC
- HIGH EFF.
APPENDIX B — PHYSICAL DATA
# Circuits / # Comp. / Type
R-410A charge A/B (lbs)
Metering device
High-press. Trip / Reset (psig)
Low-press. Trip / Reset (psig)
Material
Tube Diameter
Rows / FPI
Total face area (ft
)
2
Condensate drain conn. size
Motor Qty. / Drive Type
Max BHP
RPM range
Motor frame size
Fan Qty. / Type
Fan Diameter (in.)
Motor Qty. / Drive Type
Max BHP
RPM range
Motor frame size
Fan Qty / Type
Fan Diameter (in.)
Motor Qty. / Drive Type
Max BHP
RPM range
Motor frame size
Fan Qty. / Type
Fan Diameter (in.)
Motor Qty / Drive Type
Max BHP
RPM range
Motor frame size
Fan Qty. / Type
Fan Diameter (in.)
Motor Qty. / Drive Type
Max BHP
RPM range
Motor frame size
Fan Qty. / Type
Fan Diameter (in.)
61
50TCQD17
2 / 2 / Scroll
16.0 / 16.5
TXV
630 / 505
24 / 45
Cu / Al
/
-in.
3
8
3 / 15
19.56
/
-in.
3
4
1 / Belt
2.9
514-680
56
2 / Centrifugal
15 X 15
1 / Belt
3.7
679-863
56
2 / Centrifugal
15 X 15
1 / Belt
4.9
826-1029
56
2 / Centrifugal
15 x 15
50TCQD24
2 / 2 Scroll
23.4 / 23.4
TXV
630 / 505
24 / 45
Cu / Al
/
-in.
3
8
4 / 15
22
/
-in.
3
4
1 / Belt
4.9
690-863
56
2 / Centrifugal
15 X 15
1 / Belt
6.5 / 6.9 / 7.0 / 8.3
835-1021
184T
2 / Centrifugal
15 x 15
1 / Belt
10.5 / 11.9 / 11.9 / 11.0
941-1176
213T
2 / Centrifugal
15 x 15