Scroll Compressor Replacement; Refrigeration System - Trane IntelliPak with Symbio 800 Installation, Operation And Maintenance Manual

Commercial rooftop air conditioners
Hide thumbs Also See for IntelliPak with Symbio 800:
Table of Contents

Advertisement

Service and Maintenance
straighten any coil fins which were inadvertently bent
during the cleaning process.

Scroll Compressor Replacement

The compressor manifold system was purposely designed
to provide proper oil return to each compressor. The
refrigerant manifold system must not be modified in any
way.
Note: Altering the compressor manifold piping may cause
oil return problems and compressor failure.
Should a compressor replacement become necessary and
a suction line filter is to be installed, install it a minimum of
16 or 25 inches upstream of the oil separator tee. See
Figure 63, p.
110.
Important: Do Not release refrigerant to the atmosphere! If
adding or removing refrigerant is required, the
service technician must comply with all
Federal, State and local laws. Refer to general
service bulletin MSCU-SB-1 (latest edition).
Figure 63. Suction line filter installation

Refrigeration System

WARNING
R-410A Refrigerant under Higher
Pressure than R-22!
Failure to use proper equipment or components as
described below, could result in equipment failing and
possibly exploding, which could result in death,
serious injury, or equipment damage.
The units described in this manual use R-410A
refrigerant which operates at higher pressures than R-
22. Use ONLY R-410A rated service equipment or
components with these units. For specific handling
concerns with R-410A, please contact your local
Trane representative.
110
WARNING
Refrigerant under High Pressure!
Failure to follow instructions below could result in an
explosion which could result in death or serious
injury or equipment damage.
System contains refrigerant under high pressure.
Recover refrigerant to relieve pressure before
opening the system. See unit nameplate for
refrigerant type. Do not use non-approved
refrigerants, refrigerant substitutes, or refrigerant
additives.
Refrigerant Evacuation and Charging
NOTICE
Compressor Damage!
Failure to follow instructions below result in
permanent damage to the compressor.
The unit is fully charged with R-410A refrigerant from
the factory. However, if it becomes necessary to
remove or recharge the system with refrigerant, it is
important that the following actions are taken.
RT-SVX063G-EN