Units on the CCN can be monitored from the space using
the RJ11 connector provided with the space sensor, if desired.
To wire the RJ11 connector into the CCN (Fig. 26):
IMPORTANT: The cable selected for the RJ11 connector
wiring MUST be identical to the CCN communication bus
wire used for the entire network. Refer to Table 5 for
acceptable wiring.
1. Cut the CCN wire and strip ends of the red (+), white
(ground), and black ( ) conductors. (If another wire color
scheme is used, strip ends of appropriate wires.)
2. Insert and secure the red (+) wire to terminal 5 of the
space temperature sensor terminal block.
3. Insert and secure the white (ground) wire to terminal 4 of
the space temperature sensor.
4. Insert and secure the black ( ) wire to terminal 2 of the
space temperature sensor.
5. Connect the other end of the communication bus cable to
the remainder of the CCN communication bus.
NOTE: See Fig. 27 for space temperature averaging.
J6
RED
6
BLK
7
J6
RED
6
BLK
7
LEGEND
Factory Wiring
Field Wiring
RED
BLK
RED
BLK
SENSOR 1
SPACE TEMPERATURE AVERAGING — 4 SENSOR APPLICATION
SENSOR 1
SENSOR 4
SENSOR 7
SPACE TEMPERATURE AVERAGING — 9 SENSOR APPLICATION
Fig. 27 — Space Temperature Averaging
SPT
SENSOR
SEN
Fig. 25 — Typical SPT Wiring
TO CCN
COMM 1
BUS (PLUG)
AT UNIT
Fig. 26 — CCN Communications Bus Wiring to
Optimal Space Sensor RJ11 Connector
RED
BLK
SENSOR 2
SENSOR 3
RED
BLK
SENSOR 2
RED
BLK
SENSOR 5
RED
BLK
SENSOR 8
22
SEN
SET
T-55 SPACE
SENSOR
CCN+
CCN GND
CCN-
RED
BLK
SENSOR 4
RED
BLK
SENSOR 3
RED
BLK
SENSOR 6
RED
BLK
SENSOR 9
LVT
21
22
23
6
5
4
3
2
1