Before operating the unit, make sure the installation has solar kit..................15 been carried out correctly by a professional Daikin dealer. Decision flow of heating the domestic water by booster heater ..16 If you feel unsure about operation, contact your Daikin dealer for advice and information.
The piping between heating circuit and solar kit connection shall be copper piping, at least 1.64 ft (0.5 m) long and properly insulated. Due to heat conduction, the piping can become very hot. Installation and operation manual EKSOLHWAVJU Solar kit for air to water heat pump system 4PW54234-1...
123°F (51°C), all piping shall be properly insulated to avoid any possible (injury) burn. All used parts shall withstand the minimum technical specifications mentioned under "Technical specifications" on page EKSOLHWAVJU Installation and operation manual Solar kit for air to water heat pump system 4PW54234-1...
Page 6
If the solar pump station has no hydraulic operation of the tank. connections included, install them in the field piping as shown in "General system setup" on page Installation and operation manual EKSOLHWAVJU Solar kit for air to water heat pump system 4PW54234-1...
EKHWS050 (50 gallons)(200 l) 38.58 inch (980 mm) 15.75 inch (400 mm) EKHWS080 (80 gallons)(300 l) Installation and operation manual EKSOLHWAVJU Solar kit for air to water heat pump system 4PW54234-1...
Page 9
Return connection to indoor unit. Inlet connection from solar pump station. Return connection to solar pump station. Refer to "Accessories supplied with the solar kit" on page part 5. EKSOLHWAVJU Installation and operation manual Solar kit for air to water heat pump system 4PW54234-1...
Preventive actions must be taken to ensure minimal (Field supply) exposure of the glycol to air. Installation and operation manual EKSOLHWAVJU Solar kit for air to water heat pump system 4PW54234-1...
Page 11
For EDH, EBH, EDL, EBL units only X14A A11P Mount the plastic raisers from the accessories bag on the indoor EKHB switch box backplate. 19 20 21 EKSOLHWAVJU Installation and operation manual Solar kit for air to water heat pump system 4PW54234-1...
Page 12
The distance between the thermistor cables and power supply cable must always be at least 1.97 inch (5 cm) prevent electromagnetic interference thermistor cables. Installation and operation manual EKSOLHWAVJU Solar kit for air to water heat pump system 4PW54234-1...
Page 13
Positions where PG nipples and PG nuts need to be screwed in the domestic hot water tank are indicated on figure 1 as actions 14. RESET °C 91°C YLW/GRN EKSOLHWAVJU YLW/GRN YLW/GRN EKHWS B EKHBH/X or ED/BLQ EKSOLHWAVJU Installation and operation manual...
= 1 and the heat pump is heating the domestic water tank at that moment. Refer to "Configuring your system" on page 12 for more information. Installation and operation manual EKSOLHWAVJU Solar kit for air to water heat pump system 4PW54234-1...
Page 15
This temperature can be set on the solar pump station. Put this temperature as high as possible but not higher than 176°F (80°C), as otherwise the thermal protection in the tank might trip. EKSOLHWAVJU Installation and operation manual Solar kit for air to water heat pump system...
This troubleshooting and corrective actions may only be carried out flashing, and an error code will be displayed. by your local Daikin technician. Following error codes might be related to a malfunction of your solar system. First, check also the corrective actions as mentioned in the installation manual.
Domestic Hot Water Temperature by the Solar Pump Station temperature sensor DHW T I/U Domestic Hot Water Temperature by the Indoor Unit temperature sensor Booster Heater EKSOLHWAVJU Installation and operation manual Solar kit for air to water heat pump system 4PW54234-1...
Domestic Hot Water Temperature by the Solar Pump Station temperature sensor DHW T I/U Domestic Hot Water Temperature by the Indoor Unit temperature sensor Booster Heater Installation and operation manual EKSOLHWAVJU Solar kit for air to water heat pump system 4PW54234-1...