Swimming Pool Functions; Heat Pump Functions - Fujitsu Waterstage Comfort Series Maintenance Document

Air to water heat pump, refrigerant r410a inverter, outdoor/hydraulic unit
Table of Contents

Advertisement

Split system single phase type
DHW mode
Holiday
status
Off
x
On
Yes
On
No
On
No
On
No
On
No
On
No
On
No
On
No
x = indifferent
Information:
Release by low tariff input always triggers forced DHW
charging
If the low tariff input EX2 has not been configured and
release via OPK has nevertheless been set, the DHW
level will either continuously remain on reduced or will
follow time program 4
Legionella Function
Line N°
Programming line
1640
Legionella function
1641
Legionella function periodically
1642
Legionella function weekday
Legionella function
• Periodically
The legionella function occurs repeatedly according to
the adjusted periodicity (command line 1641)
• Fixed weekday
The legionella function can be activated on a fixed day of
the week (command line 1642) With this setting, heating
up to the legionella setpoint occurs on the scheduled day
of the week, regardless of the storage tank temperatures
during the previous period

4 4 1 Swimming Pool Functions

Line N°
Programming line
2056
Setpoint source heating
The controller enables a swimming pool to be heated
by the heat pump An individual setpoint can be set by
means of parameter 2056, which appears when the
swimming pool function is activated by parameter 6046
being set to "Swimming pool release"
Use of input H33 requires an extension to be connected
to the control
Maintenance document "1792 - EN"
Release (settings
Time pgm status
1620)
(Pgm 4)
x
x
...
Low tariff (OPK)
x
Low tariff (OPK)
x
Time pgm 4 or OPK
Nominal
Time pgm 4 or OPK
Reduced
Time pgm 4 or OPK
Nominal
Time pgm 4 or OPK
Reduced
Low tariff status
(Ex2)
x
x
x
x
...
x
Inactive
Active
Inactive
Inactive
Active
Active
4 4 2

Heat Pump Functions

Line N°
Programming line
2803
Overrun time cond pump
2843
Compressor off time min
2844
Switch-off temp max
2862
Locking time stage 2
2873
Compressor mod run time
2882
Release integr electric flow
2884
Release el flow at OT
2886
Compensation heat deficit
2916
Max setpoint HP DHW charg
2920
With electrical utility lock
Overrun time cond pump
When the compressor is switched off, the condenser
pump continues to run for the set overrun time
Compressor off time min
For the same reason, the compressor remains
switched off for the minimum period of time set here
Switch-off temperature maximum if the flow or the
return temperature exceeds the maximum switch-off
temperature, the compressor will be switched off The
heat pump is switched on again when the temperature
at both sensors has dropped by the "Switching diff return
temp" below the maximum switch-off temperature and
the minimum off time has elapsed
Switch-off temp max
If the flow or the return temperature exceeds the
maximum switch off temperature, the compressor will
be switched off
Locking time stage 2
When compressor is restarted, the time which keeps
minimum capacity can be adjusted. Efficiency becomes
better; however, the time of rising capacity becomes long.
Compressor mod run time
Compressor mod run time means the time of compressor
frequency indication changed from minimum to maximum
If this setting value changes to small, compressor
frequency changes more quickly
DHW mode level
Frost protection
Frost protection
...
Reduced
Nominal
Nominal
Reduced
Nominal
Nominal
- 75 -