Failures With No Error Code - Fujitsu Waterstage Comfort Series Maintenance Document

Air to water heat pump, refrigerant r410a inverter, outdoor/hydraulic unit
Table of Contents

Advertisement

Split system single phase type

2 2 2 Failures With No Error Code

Clear 35: No voltage on Hydraulic Unit
Probable causes:
Power supply fault
External causes
Faulty electrical components
Check:
2. Check for external causes on the Hydraulic Unit and outdoor unit (noise or voltage drop):
Check for any other electrical device on the same electric circuit which might cause a drop in
-
voltage.
Check for any current leaks.
-
Check for any equipment generating electromagnetic waves which interfere with the
-
communication between the Hydraulic Unit and the outdoor unit.
3. Check the electrical components:
Check that a voltage between AC 198 and AC 264 V exists between terminals 1 and 2 on the
-
Hydraulic Unit terminal block.
Check Interface PCB for :
-
either the fuse (F1).
o
or the varistor (VA1). Fault: overvoltage - external causes - power supply to be
o
checked).
-
Replace the faulty component (if the varistor is blown, the PCB must be replaced).
If all of these checks are unsuccessful, replace Interface PCB.
- 28 -
Clear 35:
1. Check the installation :
- Is the circuit breaker cut off?
- Check the wiring.
OK
OK
YES
OK
NO
Maintenance document "1792 - EN"