Hitachi RPI-8.0FSN3E Installation And Operation Manual page 11

Indoor units system free
Hide thumbs Also See for RPI-8.0FSN3E:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 7
UNITS INSTALLATION

Suction Air Filter Servicing
Air Filter Support
Removing Direction
3.1.4 Fan Performance Curve
Std. Air Filter Pressure Lost
"●" Rated Point
Fan Speed
Static Pressure
HSP
LSP (Std. Factory
Setting)
HSP: High Static Pressure
LSP: Low Static Pressure
3.1.5 Static Pressure Setting
RPI units have been provided by two Static Pressure levels regulation depending on the installation requirements:
High Static Pressure and Low Static Pressure (Std. Factory Setting) connectors are available into the Electrical Box.
Setting of Static Pressure shall be made by changing the Fan Unit connector.
5
PMML0229A rev.3 - 05/2016
Air Filter
RPI-8.0FSN3E(-f)
*
Air Flow (m3/min)
Hi
Med
Low
v1
v1
v3
v2
v2
v4
Remove the stay support (4 screws) from the
unit and pull down the Air Filter.
RPI-10.0FSN3E(-f)
*
Air Flow (m3/min)
?
N O T E
When design a duct, check to ensure that the Air volume is within
working range as indicate "Fan Performance Curve".
If the Air volume is set outside working range, water-carry-over (drop
in the ceiling or into the room), noise increases, fan motor damaged
(high temperature), insufficient Cooling/Heating capacity, phenomena
can occur.
Therefore design ducts and select the correct fan speed in order to
keep the unit running in the accepted working range.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rpi-10.0fsn3eRpi-8.0fsn3e-fRpi-10.0fsn3e-f

Table of Contents