Installation Location - Trane 4MXC8512B10N0 Installer Manual

Table of Contents

Advertisement

Installation Location

Indoor Unit
Adequate Support Required!
The wall/ceiling structure must be adequate to support 4 times the weight of the unit.
Failure to ensure adequate structural support could result in the unit falling from its
location which could result in death, serious injury, or equipment or property-only damage.
1. Avoid locating the indoor unit where the return and/or supply air may be obstructed.
2. Select an installation location where it is easy to drain the condensing water from
the indoor unit and where it will be easy to route refrigerant lines and communication
cabling to the outdoor unit.
3. Keep the indoor unit far away from heat sources, vapor and flammable gas.
4. It is not recommended that this unit be installed in or near a kitchen environment.
If adequate distance from the kitchen cannot be achieved, the kitchen must have
adequate ventilation to prevent contamination of the units external and internal working
parts.
5. Be sure that the installation of the indoor unit conforms to the installation dimension
diagram.
6. Ensure the installation is horizontally level.
7. Be sure to leave enough space to allow access for routine maintenance; clearance
between the bottom of the indoor unit and the floor should not be less than 71 inches.
8. Install in a location where the unit is more than 3 feet away from other electronic
appliances that could cause interferance such as television, audio devices, etc.
9. Select a location where air filters can be easily removed and replaced.
10. When installing the threaded rod or bolt, check if the installation location can withstand
4 times the weight of the units. If not, reinforce before installation. (Refer to the
installation template and locate where it should be reinforced)
For instructions on installing the outdoor unit please refer to the installation guide
supplied with the selected outdoor unit for your application.
WARNING
9
Cassette Unit

Advertisement

Table of Contents
loading

This manual is also suitable for:

4mxc8518b10n04mxc8524b10n0