Troubleshooting; To Clear An Alarm; Fault Detection And Diagnostics (Fdd); Certification - Trane BAYECON355 Series Installation Manual

0 to 100% low leak economizer – downflow
Table of Contents

Advertisement

N N o o t t e e s s : :
The checkout tests can all be performed at
the time of installation or any time during
the operation of the system.
To disable economizer for functional testing
(optional), use 10 mm wrench to loosen
shaft coupling on actuator. After testing,
securely tighten coupling onto damper shaft
using minimum 120 lb-in. (13.6 Nm) to
maximum 180 lb-in. (20.3 Nm) torque.

Troubleshooting

W W A A R R N N I I N N G G
H H a a z z a a r r d d o o u u s s V V o o l l t t a a g g e e ! !
F F a a i i l l u u r r e e t t o o d d i i s s c c o o n n n n e e c c t t p p o o w w e e r r b b e e f f o o r r e e s s e e r r v v i i c c i i n n g g c c o o u u l l d d
r r e e s s u u l l t t i i n n d d e e a a t t h h o o r r s s e e r r i i o o u u s s i i n n j j u u r r y y . .
D D i i s s c c o o n n n n e e c c t t a a l l l l e e l l e e c c t t r r i i c c p p o o w w e e r r , , i i n n c c l l u u d d i i n n g g r r e e m m o o t t e e
d d i i s s c c o o n n n n e e c c t t s s b b e e f f o o r r e e s s e e r r v v i i c c i i n n g g . . F F o o l l l l o o w w p p r r o o p p e e r r
l l o o c c k k o o u u t t / / t t a a g g o o u u t t p p r r o o c c e e d d u u r r e e s s t t o o e e n n s s u u r r e e t t h h e e p p o o w w e e r r
c c a a n n n n o o t t b b e e i i n n a a d d v v e e r r t t e e n n t t l l y y e e n n e e r r g g i i z z e e d d . . V V e e r r i i f f y y t t h h a a t t n n o o
p p o o w w e e r r i i s s p p r r e e s s e e n n t t w w i i t t h h a a v v o o l l t t m m e e t t e e r r . .
Table 10. FDD troubleshooting
Air temp. sensor
TESTS
Damper Stuck
Open
Damper Stuck at
Minimum
Bad or
Unplugged
Actuator
Sensor Hard
Failure
Actuator
Mechanically
Disconnected

To Clear an Alarm

Once the alarm has been identified and the cause has
been removed (e.g. replaced faulty sensor), the alarm
can be cleared from the display.
1. Navigate to the desired alarm.
2. Press
.
3. "ERASE?" is displayed.
4. Press
.
5. "ALARM ERASED" is displayed.
RT-SVN044A-EN
Not economizing when
failure/
it should
fault
x
x
x
x
x
N N O O T T I I C C E E
C C o o m m p p r r e e s s s s o o r r D D a a m m a a g g e e ! !
F F a a i i l l u u r r e e t t o o e e n n s s u u r r e e e e n n o o u u g g h h t t i i m m e e f f o o r r c c o o m m p p r r e e s s s s o o r r
s s t t a a r r t t - - u u p p a a n n d d s s h h u u t t d d o o w w n n b b e e t t w w e e e e n n c c h h e e c c k k o o u u t t t t e e s s t t s s
c c o o u u l l d d r r e e s s u u l l t t i i n n c c o o m m p p r r e e s s s s o o r r d d a a m m a a g g e e . .
D D o o n n o o t t s s h h o o r r t t - - c c y y c c l l e e c c o o m m p p r r e e s s s s o o r r s s . .
The economizer controller provides alarm messages
that display on the 2-line LCD.
If one or more alarms are present and there has been
no keypad activity for at least 5 minutes, the Alarms
menu displays and cycles through the active alarms.
You can also navigate to the Alarms menu at any time.
N N o o t t e e : : Upon power up, the module waits 60 minutes
before checking for alarms. This allows time for
all the configured devices (e.g. sensors, actuator)
to become operational. The exception is the MA
sensor which will alarm immediately.
FAULTS
Damper not
Economizing when it
modulating
should not
x
x
x
x
6. Press
(Menu Up) to complete the action and
return to the previous menu.
N N o o t t e e : : If an alarm still exists after you clear it, it
redisplays within 5 seconds.
Fault Detection and Diagnostics
(FDD) Certification
The JADE controller is a certified FDD product (HJW10)
by California Title 24, Part 6.
E E c c o o n n o o m m i i z z e e r r C C o o n n t t r r o o l l l l e e r r
Excess outdoor air
x
x
x
x
x
x
x
19