Sequence Of Operation - Trane BAYECON353 Series Installation Instructions Manual

0 to 100% low leak economizer - downflow foundation packaged cooling and gas/electric 3 to 5 tons
Table of Contents

Advertisement

Economizer Controller
Table 4.
Controller menu structure (continued)
Menu
Parameter
MAT SENS ERR
CO
SENS
2
OAT SENS
DA ENTHL ERR
SYS ALARM
(e)
ALARMS(_)
ACT UNDER
ACT OVER
ACT
STALLED(c)
(a) When values are displayed, pressing and holding the Up or Down button causes the display to automatically increment.
(b) N/A = Not Applicable
(c) This parameter is directly associated with the LLE economizer.
(d) The Honeywell communicating actuator will report in XX.X% open versus XX.X Vdc for damper out.
(e) Alarms display only when they are active. The menu title "ALARMS (_)" includes the number of active alarms in parenthesis ().

Sequence of Operation

Table 5.
Dry bulb operation no DCV (CO
OA Good to
DCV
economize?
None
No
None
Yes
Table 6.
Dry bulb operation with DCV (CO
OA Good to
DCV
economize?
No
Below CO
set
2
Yes
No
Above CO
set
2
Yes
18
Parameter
Parameter
Default
Range and
Value
Increment
N/A
ERR(c)
N/A
ERR(c)
N/A
N/A
N/A
V(c)
N/A
V(c)
N/A
N/A
sensor) - 1 speed fan
2
Y1-I
FAN SPD
Off
High
On
High
Off
High
On
High
On
High
sensor) - 1 speed fan
2
Y1-I
FAN SPD
Off
High
On
High
Off
High
On
High
On
High
Off
High
On
High
Off
High
On
High
On
High
Parameter
Recommended
(a)
(b)
Value
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Y1-O
0-v/Off
24-v/On
0-v/Off
0-v/Off
MIN POS to Full- Open
24-v/On
MIN POS to Full- Open
Y1-O
0-v/Off
24-v/On
0-v/Off
0-v/Off
VENTMIN to Full- Open
24-v/On
VENTMIN to Full- Open
0-v/Off
VENTMIN to VENTMAX
24-v/On
VENTMIN to VENTMAX
0-v/Off
VENTMIN to VENTMAX
0-v/Off
VENTMIN to Full- Open
24-v/On
VENTMIN to Full- Open
Notes
DA ENTHL ERR is not available
When AUX1-O is set to SYS and there is any alarm
the AUX1-O terminal has 24 Vac out
Voltage received by Actuator is above expected
range
Voltage received by Actuator is below expected
range
Actuator stopped before achieving commanded
position
Occupied
Unoccupied
MIN POS
MIN POS
MIN POS
Closed to Full-Open
Closed to Full-Open
Occupied
VENTMIN
VENTMIN
VENTMIN
Closed to Full-Open
Closed to Full-Open
Closed to Full-Open
Closed to Full-Open
Closed
Closed
Closed
Unoccupied
Closed
Closed
Closed
Closed
Closed
Closed
ACC-SVN203C-EN