(2) Outdoor units

Item
Power source
Nominal cooling capacity (range)
Nominal heating capacity (range)
Operation
Sound power level
data
Sound pressure level
Silent mode sound pressure level
Exterior dimensions (Height × Width × Depth)
Exterior appearance
( Munsell color )
Net weight
Compressor type & Q'ty
Compressor motor (Starting method)
Refrigerant oil (Amount, type)
Refrigerant (Type, amount, pre-charge length)
Heat exchanger
Refrigerant control
Fan type & Q'ty
Fan motor (Starting method)
Air flow
Shock & vibration absorber
Electric heater
Safety equipments
Refrigerant piping size ( O.D. )
Connecting method
Installation
Attached length of piping
Insulation for piping
data
Refrigerant line (one way) length
Vertical height diff. between O.U. and I.U.
Drain hose
IP number
Standard accessories
Option parts
Note (1) The data are measured at the following conditions.
Item
Indoor air temperature
DB
Operation
Cooling
27˚C
Heating
20˚C
(2) This air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat
higher due to ambient conditions.
(4) The operation data indicate when the air-conditioner is operated at 230V 50Hz or 220V 60Hz.
Model
kW
kW
Cooling
Heating
Cooling
dB(A)
Heating
mm
kg
kW
kg
R410A 3.8kg in outdoor unit (incl. the amount for the piping of : 30m)
W
Cooling
3
m
/min
Heating
W
mm
m
m
m
Max.30m (Outdoor unit is higher)
Outdoor air temperature
WB
DB
19˚C
35˚C
7˚C
-
FDC100VN
1 Phase 220-240V 50Hz / 220V 60Hz
10.0 [ 4.0(Min.)-11.2(Max.)]
11.2 [ 4.0(Min.)-12.5(Max.)]
70
49
845×970×370
Stucco white
( 4.2Y7.5/1.1) near equivalent
81
RMT5126MDE2×1
Direct line start
0.9 M-MA68
Straight fin & inner grooved tubing
Electronic expansion valve
Propeller fan ×1
86 < Direct line start >
75
73
Rubber sleeve (for compressor)
20 (Crank case heater)
Internal thermostat for fan motor.
Abnormal discharge temperature protection.
Liquid line: φ 9.52 (3/8")
Gas line: φ 15.88 (5/8")
Flare piping
Necessary (both Liquid & Gas lines)
Max.50m
Holes size φ 20 × 3pcs
IP24
Edging
Standards
WB
24˚C
ISO5151-T1
6˚C
432
-
'15 • PAC-T-236
Max.15m (Outdoor unit is lower)
The pipe length is 7.5m.
PFA004Z024
A