Basic Procedure And Prerequisites; Configuration - Siemens SIRIUS 3RB24 Manual

Protection devices electronic overload relay
Hide thumbs Also See for SIRIUS 3RB24:
Table of Contents

Advertisement

Configuring
5.1 Configuring the IO-Link
5.1.3.2

Basic procedure and prerequisites

Basic procedure when configuring IO-Link master and IO-Link devices with the S7-PCT Port
Configuration Tool (stand-alone)
1. You configure the connected IO‑Link devices with the S7-PCT Port Configuration Tool.
Requirements
• The S7-PCT Port Configuration Tool is installed on the PG/PC.
You can either install S7-PCT together with STEP 7 V5.4 SP5 or higher or STEP 7 TIA Portal
V12.0 or higher, or you can download it from the Internet
support.industry.siemens.com/cs/ww/en/view/32469496).
• IO‑Link IODD files (IO Device Description) are installed in the S7-PCT hardware catalog. All
current IODD files of the SIRIUS devices are available on the Internet
support.industry.siemens.com/cs/ww/en/ps/15851/dl).
IODD files for V1.0 and V1.1 are available for the combination of an IO‑Link master and an
IO‑Link device according to the IO‑Link communication specification V1.1. You may need
IODD files according to the communication specification V1.0 when replacing devices in
existing installations.
Note
Configuring with S7-PCT stand-alone is not possible for the CPU versions of the ET 200.
5.1.3.3

Configuration

Configuring the IO-Link device with the S7-PCT Port Configuration Tool
1. Start the S7‑PCT Port Configuration Tool.
2. Create a new project or open an existing project as described in the online help.
3. Double-click to select a bus category (PROFIBUS DP / PROFINET IO).
4. Double-click to select an IO-Link master.
5. Select the IO-Link device in the component catalog of the S7‑PCT Port Configuration Tool.
6. Drag the IO‑Link device out of the component catalog to the required port of the IO‑Link
master.
7. Load the configuration into the IO-Link master before parameterizing the IO-Link device.
8. Start by parameterizing the IO‑Link device.
More information is available in the S7-PCT online help.
Note
To be able to access the IO-Link master or an IO-Link device online, communication between
the ET 200 and the higher-level controller must be active (BF LED on ET 200 interface module
is off).
44
(https://
SIRIUS 3RB24 electronic overload relay for IO-Link
Equipment Manual, 07/2022, NEB969165602000/RS-AA/003
(https://

Advertisement

Table of Contents
loading

Table of Contents